Power Circuit Breakers Type DSII and 
SPB with OPTIM Trip Units

 

Electronic Trip Units

 

General Description

 

Cutler-Hammer offers the most comprehen-
sive range of electronic trip units in the indus-
try for power circuit breakers. The UL listed 
OPTIM electronic trip units are true RMS 
sensing and can be applied in any SPB or 
DSII breakers. 

Digitrip electronic trip units are ac devices 
that employ microprocessor-based technol-
ogy that provides a true RMS current sensing 
means for proper correlation with thermal 
characteristics of conductors and equipment. 
The primary function of the Digitrip elec-
tronic trip unit is to provide circuit protection. 
This is achieved by analyzing the secondary 
current signals received from the circuit 
breaker current sensors and initiating trip 
signals to the circuit breaker trip unit when 
pre-set current levels and time delay settings 
are exceeded. By sampling the current wave-
form at various points on the wave and calcu-
lating true RMS current, the Digitrip is able to 
reduce nuisance tripping events due to non-
sinusoidal wave shapes. 

Electronic trip units are applied to distribu-
tion systems when high standards of protec-
tion and coordination are called for. In 
addition, electronic trip units can provide fur-
ther enhanced features such as alarming, 
diagnostics, system monitoring and 
communications. 

Cutler-Hammer RMS sensing trip units for 
power breakers fall into two main categories: 

 

 

Front adjustable trip units: Digitrip RMS 
510, 610, 810, 910

 

 

Programmable trip units:  Digitrip OPTIM 
750, 1050

 

Programmable Trip Units

 

OPTIM trip units are electronic trip units that 
have up to ten time-current setting options 
that are programmed electronically by the 
use of a programming device. Trip units are 
readily accessible from the front of the break-
ers. Programmability means more settings, 
better accuracy, faster configuration, remote 
accessibility, higher system security, and the 
ability to apply limitless software. The appli-
cation for programmable trip units would be 
high integrity distribution systems that re-
quire superior levels of system coordination 
coupled with system alarming, diagnostics 
and monitoring. 

Digitrip OPTIM for power breakers are avail-
able in three configurations:

-

Long time, short time, and instanta-
neous (LSI)

-

Long time, short time, instantaneous 
and ground fault protection (LSIG)

-

Long time, short time, instantaneous 
and ground fault alarm (LSIA)

For maximum selectability, OPTIM trip units 
allow the user to disable either short time or 
instantaneous functions, but not both.

 

Rating Plugs

 

Rating plugs provide a means to establish 
the breaker’s continuous current rating. Rat-
ing plugs are unique to a particular breaker 
type, and are color coded to make it easy to 
match the correct rating plug with the correct 
circuit breaker type. Rating plugs are fixed 
type, and are interchangeable so that amp 
ratings can be changed simply by changing 
from one plug to another in a given breaker. 
The same rating plug can be applied to both 
50 and 60 Hz distribution systems. SPB plugs 
are interlocked with the breaker frame to pre-
vent putting the wrong plug into the wrong 
frame size.

Rating plugs are available down to an ampere 
value of half the sensor rating. Sensors are 

selectable on DS breakers and on SPB break-
ers are equal to the breaker frame rating. The 
plug value is referred to as I

 

n

 

 

Time-Current Curve Shaping

 

All Digitrip OPTIM settings are continuously 
adjustable, allowing virtually an infinite num-
ber of possibilities within setting ranges. 
Ranges are based on the plug rating I

 

n

 

 and 

the long delay pickup setting I

 

r

 

. For ease of 

use all pickup values are programmed in 
amps rather than in multiples of I

 

n

 

 or I

 

r

 

Table 1 illustrates available setting ranges. 

For improved system coordination OPTIM 
features a new setting not available on previ-
ous models of Digitrip. The I

 

4

 

t long delay 

slope will provide superior coordination with 
upstream fuses and transformer damage 
curves.

 

OPTIM 750

 

 

RMS Sensing

 

 

10 Functions

 

 

Programmable

 

 

Load Monitoring

 

 

Diagnostics

 

 

Communications

 

OPTIM 1050

 

 

RMS Sensing

 

 

10 Functions

 

 

Programmable

 

 

Load Monitoring

 

 

Diagnostics

 

 

Communications

 

 

Power and Energy Monitoring

 

 

Harmonics

 

Interchangeable rating plugs establish the circuit breaker’s continuous ampere rating. Different types and 
ratings are available to match the desired ampere rating and type of circuit breaker into which a Digitrip 
RMS trip unit is installed. The rating plugs are suitable for use on either 50 or 60 Hz system applications. 
Rating plugs may be applied as low as 50% of sensor rating.

Summary of Contents for Digitrip OPTIM 750

Page 1: ...PTIM for power breakers are avail able in three configurations Long time short time and instanta neous LSI Long time short time instantaneous and ground fault protection LSIG Long time short time inst...

Page 2: ...a long delay setting Ir moves the whole curve including the short time portion to provide closer protection for bus and cables Depen dent curve shaping provides a wider range of available settings OPT...

Page 3: ...trip occurs OPTIM remembers the heating effect of this overload In the event that the current levels again exceed the pickup set point before the circuit has had time to cool from the original pickup...

Page 4: ...harmon ics and other related parameters with a high level of accuracy Current Monitoring OPTIM 750 and 1050 Digitrip OPTIM 750 and 1050 trip units are ca pable of monitoring currents in individual ph...

Page 5: ...no trip testing can be carried out with the breaker in the connected cell position using an OPTIMizer a BIM or IMPACC An Auxiliary Power Module can be provided for bench testing Digitrip OPTIM 750 an...

Page 6: ...Westinghouse Dig itrip OPTIM trip units for SPB or DS circuit breakers with the following features Interchangeable rating plugs shall establish the continuous trip ratings of each circuit breaker Rat...

Page 7: ...ional auxiliary power module to allow the breaker trip unit to be bench tested with a 120 volt external power source A hand held programming unit shall be pro vided to set change the network communica...

Reviews: