background image

218

March 1996

Power Circuit Breakers Type DSII and 
SPB with OPTIM Trip Units

Typical Specifications

cuit shall be included to prevent the breaker 
being closed and latched onto a faulted 
circuit.

The trip unit shall have an information system 
that utilizes battery backed-up LED's to indi-
cate mode of trip following an automatic trip 
operation. The indication of the mode of trip 
shall be retained after an automatic trip. A trip 
reset button shall be provided to turn off the 
LED indication after an automatic trip. A test 
pushbutton shall energize an LED to indicate 
battery status. 

Circuit breakers shall be provided with a 
power/relay module to supply control power. 
Internal relays shall provide contacts for 
remote indication of the mode of trip (long 
delay, short circuit, ground fault) and high load. 

 A red LED shall be provided on the face of the 
trip unit and pre-set to flash on and off when 
an adjustable high load level is exceeded. 
A time delay shall be provided to avoid 
nuisance alarms.

The microprocessor-based trip units shall be 
capable of monitoring the following data:

Instantaneous value of phase, neutral and 
ground current

Minimum and maximum current values

Average demand current

System diagnostic information such as 
alarms and cause of trip

Approximate level of fault current that 
initiated an automatic trip operation

The monitored data shall be displayed by a 
hand-held programmer, a breaker interface 
module or a remote computer. 

The trip unit shall be capable of two-way com-
munication via a network twisted pair for re-
mote monitoring and control. The trip unit 
shall be provided with a programmable ad-
dress. Transmittable parameters shall include 
protection settings, individual phase, neutral 
and ground current, minimum and maximum 
currents, average demand current breaker 
status (open/closed/tripped), trip events and 
mode of trip; information on external trip net-

work commands, data or program memory 
test failure, missing or defective rating plug, 
test push-button operation, or communica-
tion failure. The breaker shall be capable of 
responding to open and close commands via 
the communication network. Where indicat-
ed, provide electrical operators which re-
spond to a close command via the 
communication network. 

The trip unit shall contain test capability. Test-
ing shall be carried out by using a hand-held 
programmer, a breaker interface module or a 
remote computer to select the values of test 
current within a range of available settings. 
The basic protection functions shall not be 
affected during test operations. The breaker 
may be tested in either the “Trip” or “No trip” 
test mode. Provide an optional auxiliary 
power module to allow the breaker trip unit to 
be bench tested with a 120 volt external 
power source.
 
A hand held programming unit shall be pro-
vided to set/change the network communica-
tion breaker address for each device, set the 
system baud rate, distribution frequency, 
display breaker information and display 
monitored values. In addition, provide pass-
word protection for programming time-
current set points and to perform functional 
testing of phase and ground trip characteris-
tics. The programmer shall be self powered 
by an internal battery. Provide one hand-held 
programming unit when other means of 
programming the circuit breakers are not 
provided.

Provide a local area network connecting each 
circuit breaker trip unit to a breaker interface 
module (BIM). The BIM shall be capable of 
changing the network communication 
breaker address for each device, setting the 
system baud rate and distribution frequency, 
displaying breaker information and display-
ing monitored values. In addition, provide 
password protection for programming time 
current set points, and to perform functional 
testing of phase and ground trip characteris-
tics. The BIM shall have help message 
capabilities and shall communicate informa-
tion for up to fifty devices including Digitrip 

OPTIM, 810, and 910 trip units and energy 
sentinels. Provide a 30-volt DC power supply 
for the BIM which is to be mounted within the 
assembly. Provide a product operated net-
work interface (PONI) for the BIM to commu-
nicate via the IMPACC network to a remote 
computer.

Provide Cutler-Hammer/Westinghouse 
Digitrip OPTIM 750 Trip Units

Note to Specifier — For trip units with the 
additional functions of the Digitrip OPTIM 
1050 for SPB or DSII circuit breakers, insert 
the following:

The microprocessor-based trip units shall be 
capable of monitoring the following data:

Peak demand (Megawatts)

Present demand (Megawatts)

Reverse power flow

Energy consumption (Megawatt-hours)

Reverse energy consumption

Power Factor

Percentage harmonic content

Total harmonic distortion (THD) 

The monitored data shall be displayed by a 
hand-held programming unit, a breaker inter-
face module or a remote computer. 

Circuit Breakers shall be provided with a 
potential transformer module, suitable for 
operation up to 600 volts. The primary of the 
potential transformer module shall be con-
nected internally to the load side of the circuit 
breaker through a dielectric disconnect plug.

The trip unit shall be capable of two-way 
communication via a network twisted pair for 
remote monitoring and control. Transmitta-
ble parameters shall include the addition of 
power and energy values, line-to-line voltage, 
power factor, total harmonic distortion, 
harmonic content and waveform capture, via 
the IMPACC communication network .     

Provide Cutler-Hammer/ Westinghouse
Digitrip OPTIM 1050 Trip Units.

Summary of Contents for Digitrip OPTIM 750

Page 1: ...PTIM for power breakers are avail able in three configurations Long time short time and instanta neous LSI Long time short time instantaneous and ground fault protection LSIG Long time short time inst...

Page 2: ...a long delay setting Ir moves the whole curve including the short time portion to provide closer protection for bus and cables Depen dent curve shaping provides a wider range of available settings OPT...

Page 3: ...trip occurs OPTIM remembers the heating effect of this overload In the event that the current levels again exceed the pickup set point before the circuit has had time to cool from the original pickup...

Page 4: ...harmon ics and other related parameters with a high level of accuracy Current Monitoring OPTIM 750 and 1050 Digitrip OPTIM 750 and 1050 trip units are ca pable of monitoring currents in individual ph...

Page 5: ...no trip testing can be carried out with the breaker in the connected cell position using an OPTIMizer a BIM or IMPACC An Auxiliary Power Module can be provided for bench testing Digitrip OPTIM 750 an...

Page 6: ...Westinghouse Dig itrip OPTIM trip units for SPB or DS circuit breakers with the following features Interchangeable rating plugs shall establish the continuous trip ratings of each circuit breaker Rat...

Page 7: ...ional auxiliary power module to allow the breaker trip unit to be bench tested with a 120 volt external power source A hand held programming unit shall be pro vided to set change the network communica...

Reviews: