Effective
10
/00
IL 33-K2C-3
Page 32
Fig. 65 Connecting the Auxiliary Switch
E.
For Kits Supplied with a Breaker Mounted CPT
Only:
Remove the 9-position External Harness
plug from the female receptacle on the Trip
Unit. Insert the black plug from the CPT
Harness into the same female receptacle.
Reinsert the External Harness Plug just re-
moved into the female receptacle on the CPT
Harness.
F.
Use the nylon wire ties provided to dress all
wires and harnesses to keep them away from
any moving parts within the Breaker. Be sure
to use at least one (1) wire tie to secure the
existing wiring harness, that was routed below
the DTA Assembly earlier in the Retrofit Pro-
cess, to the left side of the Breaker as shown.
Fig. 64 Securing the External Harness
C.
For Kits Supplied with a PT Module Only:
Connect the PT Harness to the External
Harness.
D.
For Kits Supplied with an Auxiliary Switch Only:
Connect the External Harness to the Auxiliary
Switch by routing the two (2) wires (with ring
terminals) from the External Harness to the
Auxiliary Switch mounted on the DTA Assem-
bly. Connect one (1) wire to the normally
“Open” terminal and the other wire to the
“Common” terminal of the Auxiliary Switch.