Eaton Din Rail UPS Advanced User Guide 934139—Rev A
19
C
Chhaapptteerr 88 TTrroouubblleesshhoooottiinngg
88..11
TTrroouubblleesshhoooottiinngg
Problem
Possible Cause
Solution
UPS nonresponsive
(No LEDs or alarm)
UPS is powered off
Press ON/OFF button for TWO (2)
seconds.
UPS fault
Contact Tech support.
The UPS is always operating in Battery
Mode
Input may not be properly connected.
Check the input connection.
Input fuse is open
Before reconnecting equipment,verify the
load matches the UPS capability
specified and output has short circuit
protection. Contact Tech support.
Actual backup time cannot be achieved
Battery voltage is too low
Charge the battery at least eight (8)
hours.
Overload
Remove unnecessary loads. Before
reconnecting equipment, verify the load
matches the UPS capability specified.
Battery defect
Replace the battery.
UPS fault or charger failure
Contact Tech support.
Fault code displayed.
Overload
Remove unnecessary loads. Before
reconnecting equipment, verify the load
matches the UPS capability specified.
UPS short-circuit
Contact Tech support.
UPS over temperature
Remove unnecessary loads. Before
reconnecting equipment, verify the load
matches the UPS capability specified.
Make sure the UPS is installed in a
pretested area that is free of excessive
dust and has adequate air flow. Place the
UPS away from other units at least 8int
to avoid interference. For best
performance, keep the indoor
temperature between 0°C to 50°C.
Summary of Contents for DIN24240DC
Page 5: ...2 Eaton Din Rail UPS Advanced User Guide 934139 Rev A Safety and Warnings ...
Page 11: ...8 Eaton Din Rail UPS Advanced User Guide 934139 Rev A DIN24240DC DIN24480DC Input Wiring ...
Page 15: ...12 Eaton Din Rail UPS Advanced User Guide 934139 Rev A Extended Battery Module Wiring ...
Page 17: ...14 Eaton Din Rail UPS Advanced User Guide 934139 Rev A UPS Self Test ...
Page 19: ...16 Eaton Din Rail UPS Advanced User Guide 934139 Rev A UPS Dry Contacts ...
Page 21: ...18 Eaton Din Rail UPS Advanced User Guide 934139 Rev A Storage ...
Page 23: ...20 Eaton Din Rail UPS Advanced User Guide 934139 Rev A Troubleshooting ...
Page 27: ...934139A 934139 A ...
Page 32: ...2 SAI de riel DIN de Eaton Guía de Usuario Avanzado 934139 Rev A Seguridad y Advertencias ...
Page 44: ...14 SAI de riel DIN de Eaton Guía de Usuario Avanzado 934139 Rev A Autodiagnóstico del UPS ...
Page 46: ...16 SAI de riel DIN de Eaton Guía de Usuario Avanzado 934139 Rev A Contactos Secos del UPS ...
Page 48: ...18 SAI de riel DIN de Eaton Guía de Usuario Avanzado 934139 Rev A Almacenamiento ...
Page 50: ...20 SAI de riel DIN de Eaton Guía de Usuario Avanzado 934139 Rev A Solución de Problemas ...
Page 54: ...934139A 934139 A ...
Page 75: ...18 Onduleur sur rail DIN Eaton Guide de l utilisateur avancé 934139 Rev A Entreposage ...
Page 77: ...20 Onduleur sur rail DIN Eaton Guide de l utilisateur avancé 934139 Rev A Dépannage ...
Page 81: ...934139A 934139 A ...