39
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
39
Configuration Tag 17:
Optim Trip Unit
Command
Number
INCOM
Command
Command
Description
Scan
Level
0
300
Fast Status
Poll
1
300 with 3C8
Fast Status & Flags Buffer
Poll
2
30F N=3
Current Buffer
Interleaved
3
3C9
Setpoints Buffer
Timed3
Binary
Input
Type
Description
Scan
Level
0
Status
Device On-Line
Virtual
1
Status
Open (S7-S6 state = 00)
Poll
2
Status
Closed (S7-S6 state = 01)
Poll
3
Status
Tripped (S7-S6 state = 10)
Poll
4
Status
LDPU Alarm (S7-S6 state = 11)
Poll
5
Status
Breaker Closed
Poll
Analog
Input
Type
Description
Scan
Level
0
Data
I
A
Interleaved
1
Data
I
B
Interleaved
2
Data
I
C
Interleaved
3
Data
I
G
Interleaved
4
Data
I
N
Interleaved
Counter
Input
Type
Description
Scan
Level
0
Data
Primary / Secondary / Cause
Poll
1
Data
INCOM Product ID
Poll
2
Data
Firmware Version / Revision
Timed3