4 Commissioning
4.3 Parameter settings
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
31
Table 4:
Parameter P-15
Select f-Fix Bit0
Select f-Fix Bit1
Select f-Fix Bit2
Used to select a fixed frequency with digital commands
Fixed frequencies f-Fix1, …, f-Fix8 are defined with parameters P2-01, …, P2-08.
0 = Low; 1 = High
START
Used to start/stop the drive
UP
Used to increase the speed if a digital setpoint is selected
Used together with the DOWN command.
Abbreviation
Meaning
Fixed
Bit 2
Bit 1
Bit 0
f-Fix1 (P2-01)
0
0
0
f-Fix2 (P2-02)
0
0
1
f-Fix3 (P2-03)
0
1
0
f-Fix4 (P2-04)
0
1
1
f-Fix5 (P2-05)
1
0
0
f-Fix6 (P2-06)
1
0
1
f-Fix7 (P2-07)
1
1
0
f-Fix8 (P2-08)
1
1
1
P-15
DI1
(Terminal 2)
DI2
(Terminal 3)
DI3/AI2
(Terminal 4)
DI4/AI1
(Terminal 6)
0
ENA
No function
No function
No function
1
ENA
No function
No function
No function
2
ENA
No function
No function
No function
3
ENA
Select BUS REF/f-Fix
EXTFLT
AI1 REF
4
ENA
No function
No function
No function
5
ENA
No function
Select f-Fix1 / f-Fix2
No function
6
ENA
Select BUS REF/AI REF
EXTFLT
AI1 REF
7
ENA
Select BUS REF/Keypad REF
EXTFLT
AI1 REF
8
ENA
No function
No function
No function
9
ENA
No function
No function
No function
10
ENA
No function
No function
No function
11
ENA
No function
No function
No function
12
ENA
No function
No function
No function
13
ENA
No function
EXTFLT
No function
14
15
ENA
f-Fix1/Select BUS REF
Select Fire Mode/Normal OP
Pre-set speed 4/2
16
ENA
f-Fix4/Select BUS REF
Select Fire Mode/Normal OP
No function
17
ENA
Keypad REF/Select BUS REF
Select Fire Mode/Normal OP
No function