45
Product safety
The UPS connection instructions and operation described in the manual must be
followed in the indicated order.
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection for 100A rating.
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The
unit can be disconnected from AC power source by opening this circuit breaker.
An additional AC contactor is used for backfeed protection and must comply with
IEC/EN 62040-1 (the creep age and clearance distances shall meet the basic insulation
requirements for pollution degree 2).
Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
Check that the indications on the rating plate correspond to your AC powered system
and to the actual electrical consumption of all the equipment to be connected to the
system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment
and shall be easily accessible
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +60°C with battery(-15°C to
+40°C without battery).
Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
All handling operations will require at least two people (unpacking, lifting, installation
in rack system).
Straps are provided only for unpacking manually the unit from the carton; don’t use
the straps to carry the unit around. The unit can slip from the straps during handling
(risk of injury and product damage):
- keep 12in / 30cm minimum distance between the straps
- lift the unit carefully and keep it at low height
- keep the unit horizontal during unpacking.
Summary of Contents for DXRT 10KS31-IN Series
Page 1: ...Eaton DXRT 10KXL31 系列 系列 系列 系列 在线式 UPS ...
Page 11: ...10 4 安装尺寸图参考如下 塔式安装 1 从附件中取出脚架 向下扣成脚架 2 将LCD面板从箱体上拔出适当高度 20 30mm ...
Page 14: ...13 2 安装挂耳 注意挂耳安装方向 凹形向下 3 按如下图所示方向将 UPS 主机和电池箱放入到机架的滑道上 然后推到固定 位置 从附件中取出螺钉 将其固定在即加上 ...
Page 32: ...31 清除事件记录 该指令可以清除事件子菜单中的所有记录 请谨慎 恢复出厂设置 所有的设置将会恢复到默认的出厂状态 该指令只能在旁 路下执行 ...
Page 34: ...33 ...
Page 35: ...34 说明 如何设置输出电压 ...
Page 43: ...42 Eaton DXRT 10KS31 IN Series Online UPS ...
Page 54: ...53 2 5 Circuit diagram ...
Page 83: ...82 ...
Page 85: ...84 Example set rated output voltage value ...
Page 86: ...85 ...
Page 98: ...0 614 40029 00 ...