8
Use cable cross section and protective device specification
Model
6000H
6000HXL
10000H
10000HXL
Input L,N,
Min. conductor cross section[m
㎡
]
Max. conductor cross section[m
㎡
]
4.0
10.0
10.0
25.0
Input L,N breaker (A)
32A, 250VAC
50A, 250VAC
Input fuse (A)
30A, 250VAC
60A, 250VAC
Output L,N,
Min. conductor cross section[m
㎡
]
Max. conductor cross section[m
㎡
]
4.0
10.0
10.0
25.0
External Battery Cabinet Positive
Pole(+), Neutral pole, Negative pole(-),
Min. conductor cross section[m
㎡
]
Max. conductor cross section[m
㎡
]
4.0
10.0
10.0
25.0
External Battery Cabinet Fuse (A) in
Positive pole(+),Neutral pole,
Negative pole(-).
30A, 240VDC
50A, 240VDC
External Battery Cabinet breaker (A) in
Positive pole(+),Neutral pole,
Negative pole(-).
30A, 240VDC
50A, 240VDC
Backfeed protection device
A 2-pole disconnection device with 60A/250VAC,
less than 15s break time and min. 1.4mm clearance
will be used in final installation for backfeed
protection.
Protective Earthing conductor[m
㎡
]
Min.2.5 Min.6.0
Torque for fixing above terminals
3.95~4.97Nm
(35~44 1bf· in)
Summary of Contents for E Series DX
Page 1: ......
Page 4: ...IT 3 N 4 1 2 UPS UPS UPS UPS UPS UPS 1 3 UPS BUS UPS 1 4 UPS...
Page 5: ...1 5 UPS 3 1 2 2 1 6 6000H 6000HXL 10000H 10000HXL UPS UPS UPS OFF UPS ON...
Page 9: ...4 4 1 1 UPS 6000HXL 10000HXL 2 UPS 4 2 1 UPS 2 UPS 0 5m...
Page 23: ...8 2 12 25 C 3 5 4 6 UPS UPS 12 1 2 3 4 UPS 9 9 1 LED INV LED LED 1 LED LED UPS...
Page 24: ...2 LED 90 UPS UPS UPS UPS UPS UPS AC UPS 9 2 LED INV LED LED LED 1 UPS 4 ON 1 ON 1 2 LED...
Page 25: ...UPS 9 3 LED LED LED UPS 2 LED UPS 1 2 UPS 9 4 UPS LED...
Page 29: ...2 1000H XL Figure 1 Back View of 1K 1KS 2000H XL CE 2000H CE 2000HXL CE XL Model only XL...
Page 30: ...3000H XL CE 3000H XL CE 6000H 6000HXL XL...
Page 31: ...10000H 10000HXL...