2) Battery Charge: Fully charge the batteries of the UPS system by powering the UPS
system from the utility mains supply for 1-2 hours. You may use the UPS system
without charging the battery in advance, but the stored energy time may be shorter
than the nominal value specified.
3) Connection Procedure of External Battery for Long Backup time Model (“XL” Model)
The unit with/ without CE markings:
a) Use the battery pack with voltage: 36Vdc for 1000HXL (3 pcs of 12V batteries),
96Vdc for 2000HXL/3000HXL (8 pcs of 12V batteries). Connection of batteries
more than or less than required will cause abnormality.
b) One end of the external battery cord is a plug for connecting the UPS and the other
end has a plug for connecting the user battery cabinet. But the unit without CE
markings is a plug for connecting the UPS and the other end has 3 (or 2) open
wires for connecting the battery pack.
c) The battery connection procedure is very important. Any incompliance may result
in the risk of electric shock. Therefore, the following steps must be strictly complied
with.
★
Connect the batteries in series to ensure proper battery voltage.
★
Do not connect the battery socket of the UPS first. Otherwise, it may cause
electric shock
d) Do not connect any load to the UPS, before connecting the UPS to utility mains
supply via input power cord make sure the UPS will be powered by the utility mains
supply.
e) Connect the battery to the external battery socket on the rear panel of the UPS via
the external battery cord, the rectifier will start to charge the battery if the UPS is
operating in line mode.
FOR the models without CE:
★
Connect the external battery cord to the battery terminal .The "+" terminal of the battery,
the black wire is connected to the "-" terminal of the battery. (Note: the green/yellow wire
is grounded for protection purpose.)
4.4
Installation for 6000H(XL)/10000H(XL)
Installation and wiring must be performed in accordance with the local electric code and the
following instructions by professional personnel.
1) Please isolate the mains supply before installation. On XL models fitted with external
battery cabinets, ensure the battery circuit breaker is also switched off.
Caution!
The output sockets of the UPS system may still be electrically live even if the power
supply system has been disconnected or the Bypass switch is on “OFF” position.
Summary of Contents for E Series DX
Page 1: ......
Page 4: ...IT 3 N 4 1 2 UPS UPS UPS UPS UPS UPS 1 3 UPS BUS UPS 1 4 UPS...
Page 5: ...1 5 UPS 3 1 2 2 1 6 6000H 6000HXL 10000H 10000HXL UPS UPS UPS OFF UPS ON...
Page 9: ...4 4 1 1 UPS 6000HXL 10000HXL 2 UPS 4 2 1 UPS 2 UPS 0 5m...
Page 23: ...8 2 12 25 C 3 5 4 6 UPS UPS 12 1 2 3 4 UPS 9 9 1 LED INV LED LED 1 LED LED UPS...
Page 24: ...2 LED 90 UPS UPS UPS UPS UPS UPS AC UPS 9 2 LED INV LED LED LED 1 UPS 4 ON 1 ON 1 2 LED...
Page 25: ...UPS 9 3 LED LED LED UPS 2 LED UPS 1 2 UPS 9 4 UPS LED...
Page 29: ...2 1000H XL Figure 1 Back View of 1K 1KS 2000H XL CE 2000H CE 2000HXL CE XL Model only XL...
Page 30: ...3000H XL CE 3000H XL CE 6000H 6000HXL XL...
Page 31: ...10000H 10000HXL...