21

8 Battery 

Maintenance 

  If the battery operates in the hot climate areas, they should be charged and discharged 

every 2 months. The standard charging time should be at least 12 hours. 

  If the batteries exceed their service life under normal conditions (3 - 5 years at 25°C 

ambient temperature).Please contact your dealer to replace them. In case that the 
battery is found in bad condition, replacement should be made. Battery replacement 
should be performed by qualified personnel. 

  Do not replace the battery individually. All the batteries should be replaced at the same 

time following the instructions of the battery supplier. 

  Normally, the batteries should be charged and discharged once every 4 to 6 months. 

Charging should begin after the UPS is turned off automatically in the course of 
discharging, the standard charging time for the standard UPS should be at least 12 
hours.  

Notes for battery disposal and battery replacement: 

1) If it is necessary to replace any connection cables, please purchase the original 

materials from the authorised distributors or service centre, so as to avoid overheat or 
spark resulting in fire due to insufficient capacity. 

2)  Do not short the positive and negative of the battery terminals, otherwise, it may result 

in electric shock or fire. 

3)  Make sure that there is no voltage before touching the batteries. The battery circuit is 

not isolated from the input potential circuit. There may be hazardous voltage between 
the battery terminals and the ground. 

4)  Even though the input breaker is disconnected, the components inside the UPS are still 

connected with the batteries, and there are potential hazardous voltages. Therefore, 
before any maintenance and repairs work is carried out, switch off the breaker of the 
battery pack or disconnect the jumper wire of connecting between the batteries. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for E Series DX

Page 1: ......

Page 2: ...1 2 2 3 4 4 1 4 2 4 3 1000H XL 2000H XL 3000H XL 4 4 6000H XL 10000H XL 5 5 1 5 2 6000H XL 10000H XL 6 6 1 6 2 6 3 6 4 25 C 7 7 1 1000H XL 2000H XL 3000H XL 7 2 6000H XL 10000H XL 8 9 9 1 9 2 9 3 9 4...

Page 3: ...3000H UPS UPS UPS 6000H 10000H UPS UPS Eaton E Series DX 1000H X XL Brand name UPS series Output capacity VA Code Batteries internal or external Nil Standard model with batteries internal XL Long back...

Page 4: ...IT 3 N 4 1 2 UPS UPS UPS UPS UPS UPS 1 3 UPS BUS UPS 1 4 UPS...

Page 5: ...1 5 UPS 3 1 2 2 1 6 6000H 6000HXL 10000H 10000HXL UPS UPS UPS OFF UPS ON...

Page 6: ...2 UPS AC DC AC UPS XL UPS 2 1 1000H 1000HXL 2000H 2000HXL 3000H 3000HXL 6000H 6000HXL 10000H 10000HXL...

Page 7: ...EFT IEC EN 61000 4 4 4 SURGE IEC EN 61000 4 5 4 CS IEC EN 61000 4 6 3 PFMF IEC EN 61000 4 8 4 IEC EN 61000 2 2 EMI 1000H XL 2000H XL 3000H XL IEC EN 62040 2 C2 IEC EN 62040 2 C2 IEC EN 61000 3 2 IEC E...

Page 8: ...PS 2 OFF OFF UPS LED UPS LED UPS N LED LED LED LED LED LED LED LED LED LED UPS LED LED LED UPS 2 LED 96 105 3 LED 76 95 4 LED 56 75 5 LED 36 55 6 LED 0 35 LED 2 LED 0 25 3 LED 26 50 4 LED 51 75 5 LED...

Page 9: ...4 4 1 1 UPS 6000HXL 10000HXL 2 UPS 4 2 1 UPS 2 UPS 0 5m...

Page 10: ...L N A 32A 250VAC 50A 250VAC A 30A 250VAC 60A 250VAC L N mm 2 mm 2 4 0 10 0 10 0 25 0 mm 2 mm 2 4 0 10 0 10 0 25 0 A 30A 240VDC 50A 240VDC A 30A240VDC 50A 240VDC 15s 1 4mm 60A 250VAC 2 mm 2 2 5 6 0 3...

Page 11: ...H 10A 2000HXL 3000H XL 16A 1 2 1000H XL 2000HXL CE UPS pcs 1000H XL 4 Nil 2000H 6 Nil 2000HXL 4 CE KC 6 CE CE KC Nil CE 3000H XL 4 CE KC 3 CE 2000HXL CE 3000H XL a b AWG14 2 1mm2 10 c d 2000HXL CE 300...

Page 12: ...2 1 2 UPS UPS UPS 3 XL CE a 1000HXL 36Vdc 12V 3 2000HXL 3000HXL 96Vdc 12V 8 b UPS CE UPS 3 2 c UPS d UPS UPS UPS e UPS UPS CE 4 4 6000H XL 10000H XL 1 XL OFF UPS...

Page 13: ...a UPS b 6000H XL UPS AWG UL1015 10AWG 4mm2 6000H XL 10mm2 10 c 10000H XL UPS AWG UL1015 8AWG 10mm2 10000H XL 25mm2 10 UPS UPS d e f g UPS h UPS i UPS UPS UPS UPS UPS j 8 UPS ON UPS k UPS UPS...

Page 14: ...UPS JPI JP2 10AWG 6mm2 UPS JP1 JP2 2 UPS a DC 240VDC 20 b UPS 3 c DC UPS d OFF 20 e 10000HXL 10000HXL f UPS UPS ON ON UPS UPS...

Page 15: ...3 a N X N UPS X UPS UPS X N X UPS 3 UPS b 25 stitches 25 3m Santak 5m 10m UPS UPS JP1 JP2 UPS 20m UPS 20 UPS 20m UPS 10...

Page 16: ...UPS 1 UPS AC a UPS ON UPS UPS b UPS ON 1 LED INV LED UPS UPS 2 UPS a UPS ON 1 b XL ON c UPS LED LED 3 UPS AC a UPS OFF 1 b UPS INV LED LED UPS c UPS UPS UPS UPS 4 UPS a UPS OFF 1 b UPS LED UPS UPS UP...

Page 17: ...5 a I UPS UPS b I 1 5 2 6000H XL 10000H XL 1 UPS UPS a b UPS JP1 JP2 c UPS UPS UPS Bypass UPS d UPS JP1 JP2 e UPS f UPS UPS 1V UPS L g UPS h UPS UPS UPS UPS UPS UPS JP2 i UPS UPS UPS Bypass UPS...

Page 18: ...j UPS UPS UPS a UPS b c UPS UPS UPS Bypass UPS UPS Bypass d UPS UPS JP1 JP2 e UPS UPS UPS f UPS UPS g BPS BPS UPS a UPS UPS Bypass b UPS OFF c UPS 2 XL 6000H XL 10000H XL...

Page 19: ...A 0 7kW 1kVA 0 7kW 2kVA 1 4kW 3kVA 2 1kW 2 6000H XL 10000H XL 6000H 6000HXL 10000H 10000HXL 6KVA 4 2KW 6KVA 4 2KW 10KVA 7KW 10KVA 7KW Hz 50 60Hz 185 266V 220 240V 30A max 30A max 50A max 50A max 0 98...

Page 20: ...H mm kg 1000H 145X400X220 14 1000HXL 145X400X220 7 2000H 192X460X340 34 5 2000HXL 192X460X340 15 3000H 192X460X340 35 5 3000HXL 192X460X340 16 6000H 260 X570 X717 90 6000HXL 260 X570 X717 35 10000H 2...

Page 21: ...7 7 1 1000H XL 2000H XL 3000H XL UPS LED UPS 180 UPS LED LED LED On I LED 4 LED UPS FAULT LED UPS 1 2 LED LED...

Page 22: ...10000H XL 1 LED 6 LED UPS UPS UPS 10 1 LED 2 5 LED UPS UPS UPS 1 LED 4 LED UPS UPS 1 LED 5 LED UPS UPS LED UPS UPS UPS 1 LED 2 LED UPS UPS UPS 1 LED LED UPS LED ON UPS UPS 10 UPS ON ON 1 UPS ON UPS UP...

Page 23: ...8 2 12 25 C 3 5 4 6 UPS UPS 12 1 2 3 4 UPS 9 9 1 LED INV LED LED 1 LED LED UPS...

Page 24: ...2 LED 90 UPS UPS UPS UPS UPS UPS AC UPS 9 2 LED INV LED LED LED 1 UPS 4 ON 1 ON 1 2 LED...

Page 25: ...UPS 9 3 LED LED LED UPS 2 LED UPS 1 2 UPS 9 4 UPS LED...

Page 26: ...10 10 1 RS232 Winpower DB 9 10 2 AS400 RS232 UPS AS400 AS400 UPS AS400 DB 9 I O 1 UPS 2 3 GND 4 5 6 7 8 UPS ON 9 I O 2 TXD 3 RXD 5 GND...

Page 27: ...11 WinPower WinPower UPS UPS UPS LAN UPS 1 http www ups software download com winpower htm 2 3 511C1 01220 0100 478DF2A WinPower...

Page 28: ...LED 1 2 3 4 5 6 7 8 9 10 1 0 35 2 36 55 3 56 75 4 76 95 5 96 105 6 0 25 7 26 50 4 8 51 75 4 9 76 95 4 10 96 100 4 11 2 12 UPS INV 13 UPS 14 15 16 17 18 Inv 19 20 BUS 21 22 BAT SCR 23 24 INV RLY 25 26...

Page 29: ...2 1000H XL Figure 1 Back View of 1K 1KS 2000H XL CE 2000H CE 2000HXL CE XL Model only XL...

Page 30: ...3000H XL CE 3000H XL CE 6000H 6000HXL XL...

Page 31: ...10000H 10000HXL...

Page 32: ...r 6000H XL 10000H XL 5 Operation 5 1 Turn on and turn off 5 2 The parallel system maintenance and operation for 6000H XL 10000H XL 6 Technical Data 6 1 Electrical specifications 6 2 Operating environm...

Page 33: ...overload the UPS e g laser printers etc to the UPS outlet sockets For 1000H 2000H 3000H Outlet sockets and battery sockets are earthed by the input power cord please insert the power cord into the mai...

Page 34: ...the qualified maintenance personnel Disconnect the batteries before carrying out any kind of service and maintenance Confirm that there is no electrical charge in the capacitor or BUS capacitor termin...

Page 35: ...ctions Equipment powered more than one source High leakage current earth connection essential before connecting supply Indiscriminate operation of switches may cause output loss or damage to equipment...

Page 36: ...e to provide the inverter power without any switching or break in supply The inverter converts the direct voltage to AC output for the load use This manual is applied for the UPSs XL Model Long backup...

Page 37: ...2040 2 C2 Radiated Emission IEC EN 62040 2 C2 Harmonic Current IEC EN 61000 3 2 Voltage Fluctuation and Flicker IEC EN 61000 3 3 Warning This is a category C2 UPS product In a residential invironment...

Page 38: ...p the mains power supply is out of tolerance BATTERY LED The orange BATTERY LED lights up when the mains power is failed and the inverter is being powered by the batteries BYPASS LED The orange BYPASS...

Page 39: ...6000HXL 10000HXL 2 If the UPS arrives damaged or there is any missing accessory please contact the carrier and dealer immediately 4 2 Notes for installation 1 The UPS must be installed in a location w...

Page 40: ...Neutral pole Negative pole Min conductor cross section m Max conductor cross section m 4 0 10 0 10 0 25 0 External Battery Cabinet Fuse A in Positive pole Neutral pole Negative pole 30A 240VDC 50A 240...

Page 41: ...CE 3 Non CE Available Besides output sockets 2000HXL CE and 3000H XL models also feature an output terminal block The wiring configuration is shown below a Remove the small cover of the terminal block...

Page 42: ...e batteries in series to ensure proper battery voltage Do not connect the battery socket of the UPS first Otherwise it may cause electric shock d Do not connect any load to the UPS before connecting t...

Page 43: ...on between the equipment which consumes electric equipment and the ground wire The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or...

Page 44: ...the data specified in the general specification d Set the battery pack breaker to OFF position and connect the 20 pieces of batteries in series e You must connect the external battery cable to the ba...

Page 45: ...ld for communication of the parallel system The length of the parallel cable is appropriate to be less than 3m this should be corrected as Santak makes available both 5m and 10m cables Strictly follow...

Page 46: ...During startup the UPS has the same action as if it is connected to utility power except that the utility power LED is not turned on and the battery LED is turned on instead 3 Turn off the UPS with ut...

Page 47: ...PS system is configured for single module mode remove the connection between JP1 and JP2 e Take apart the board of parallel ports insert one end of combine line into parallel card s slot and screw dow...

Page 48: ...parallel cover and combine line when the unit has to be removed then lock up the cover of parallel ports again g Disconnect the input switch of the remaining unit turn maintenance switch from BPS to U...

Page 49: ...KW 10KVA 7KW Frequency Hz 50 60Hz Voltage range 185 266V Voltage 220 240V Current 30A max 30A max 50A max 50A max Input Power Factor 0 98 Full load Voltage 220 240V Current 27A 27A 46A 46A Power Facto...

Page 50: ...00 95 91 86 82 78 74 70 67 6 3 Dimensions and weights Model No Dimensions W x D x H mm Net Weight kg 1000H 145X400X220 14 1000HXL 145X400X220 7 2000H 192X460X340 34 5 2000HXL 192X460X340 15 3000H 192X...

Page 51: ...if necessary LINE and BYPASS LED light up even though the power supply is available Inverter not switched on Press On Switch I INVERTER LED lights up and audible alarm beeps once every 4 seconds Mains...

Page 52: ...overloaded or the load equipment is faulty Check the loads and remove all non critical equipment Recalculate the load power and reduce the number of loads connected to the UPS Check that the loads ar...

Page 53: ...charging time for the standard UPS should be at least 12 hours Notes for battery disposal and battery replacement 1 If it is necessary to replace any connection cables please purchase the original ma...

Page 54: ...r and wait until the operation is stable before supplying power of the generator to the UPS be sure that the UPS is in idle mode Then turn on the UPS according to start up procedure After the UPS is t...

Page 55: ...utility power LED and the bypass LED are lit The displayed number of the load LEDs will be turned on in accordance with the load capacity connected The UPS will beep once every 2 minutes in bypass mod...

Page 56: ...rs can directly use UPS supervising function offered by AS400 system to realize power source management Please contact your local distributor for details The following is the pin assignment and descri...

Page 57: ...ol any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www ups software download com winpower htm 2 Choose the operation system you need and follow...

Page 58: ...in utility mode and UPS still in INV mode Beep twice every sec 13 overloaded in utility mode and UPS in bypass mode Beep twice every sec 14 Utility power abnormal 15 Overloaded in battery mode Early w...

Page 59: ...nd output socket are vary with different areas the appearance of the products is based on what it is Rear View of 1000H XL Figure 1 Back View of 1K 1KS Rear View of 2000H XL Non CE certified 2000H CE...

Page 60: ...Rear View of 3000H XL Non CE certified Rear k View of 3000H XL CE certified Rear view of 6000H Rear view of 6000HXL For XL Model only...

Page 61: ...Rear view of 10000H Rear view of 10000HXL...

Reviews: