3. Operation and Configuration
EAFR-101S Arc Point Sensor Relay User Manual
MN026005EN February 2016 www.eaton.com
Figure 11. EAFR-101S Configuration Selection 8.
3.5.1.8 Configuration Selection 8
The EAFR-101S logic Configuration 8 is utilized in the selec-
tive arc protection solution. The point sensor S1 monitors
the outgoing feeder cable compartment. S2 is used for
monitoring the corresponding feeder breaker compartment.
S3 and S4 monitor the busbar compartment. The contact T1
is responsible for tripping the circuit breaker of the outgo-
ing feeder. BI3 receives over-current information from the
EAFR-110P of the incoming feeder. BO1 sends light infor-
mation to the EAFR-110P of incoming feeder when there is
any arc fault detected by EAFR-101S. The CBFP module is
applied in this configuration.