10.4 Test Plan Example
Date:
Substation:
Switchgear:
EAFR-101S Serial Number:
Preconditions
Light Only
Light + Current
Remarks
Sensor Channel 1 Setting
Sensor Channel 2,3,4 Setting
Circuit Breaker Failure Protection (CBFP) in Use (Yes / No): 100 ms: _____ / 150 ms: ______
Object Activated
LED Indication
T1, T2, and
T3 Active
BO1 Active BO2 Active BO3 Active
Sensor Channel 1
Sensor 1
Sensor 2
Sensor 3
Sensor Channel 2
Sensor 1
Sensor 2
Sensor 3
Sensor Channel 3
Sensor 1
Sensor 2
Sensor 3
Sensor Channel 4
Sensor 1
Sensor 2
Sensor 3
BIN 1
BIN 2
BIN 3
BIN 4
BIN 5
BIN 6
Tested by:
Approved by:
otee:
N
If the revelant configuration includes the CBFP function, then the CBFP time setting is in use.
11. Troubleshooting Guide
Table 10. Troubleshooting Guide.
Problem
Check
Cross Reference
Sensor does not acti-
vate when testing.
Sensor cable wiring
Section 4 of this manual
Camera (or other test
equipment) flash intensity
Section 10 of this
manual
Trip relay(s) does not
operate even if sensor is
activated.
Dipswitch settings
Section 3.5 of this
manual
12. Technical Data
12.1 Protection
Trip time using mechanical trip relays.
7 ms*
Reset time (arc light stage).
2 ms
Protection operational after power up.
88 ms
* = Total trip time using arc light or phase/residual over-current from
EAFR-110 and arc light.