8.3.4.4 EASY512-DC-…, EASY6..-DC-.E, EASY7..-DC-...
EASY512-DC-…
EASY6..-DC-.E
EASY7..-DC-…
Digital inputs
Number
8
12
12
Inputs usable as analog inputs
I7, I8
I7, I8, I11, I12
Status display
LCD (if provided)
Potential isolation
To power supply
No
No
No
between digital inputs
No
No
No
from the outputs
Yes
Yes
Yes
Rated voltage
Nominal value
24 V DC
24 V DC
24 V DC
At signal “0”
< 5 V DC (I1 to I8)
< 5 V DC (R1 to R12)
< 5 V DC (I1 to I12)
At signal ”1”
> 8 V DC (I7, I8)
> 8 V DC
(I7, I8, I11, I12)
> 15 V DC
(I1 - I6)
> 15 V DC (R1 - R12)
> 15 V DC
(I1 - I6, I9, I10)
Input current on signal 1
3.3 mA at 24 V DC (I1 -
I6)
3.3 mA at 24 V DC (R1 -
R12)
3.3 mA at 24 V DC (I1 -
I6, I9, I10)
I7, I8 (easy7..-DC-.. also I11,
I12)
2.2 mA at 24 V DC
2.2 mA at 24 V DC
Delay time from 0 to 1
Debounce ON
20 ms
20 ms
20 ms
Debounce OFF
easy512.DC-.. I1 to I8
easy6..-DC-.. R1 to R12
easy7.._DC-.. I1 to I12
Normally 0.25 ms
Delay time from 1 to 0
Debounce ON
20 ms
20 ms
20 ms
Debounce OFF
• Normally 0.4 ms
(I1 - I6)
• Normally 0.2 ms (I7,
I8)
Normally 0.4 ms
(R1 - R12)
• Normally 0.4 ms
(I1 - I6, I9, I10)
• Normally 0.2 ms
(I7, I8, I11, I12)
Cable length (unshielded)
100 m
100 m
100 m