4 Wiring with
4.4 Analog value comparator/threshold value switch
90
Operating instructions
05/10 MN05013003Z-EN
www.eaton.com
4.4.5.4 Example: Function of the Greater than/equal to comparison
Parameter display and parameter set for Greater than/equal analog value
comparator.
Circuit diagram with analog value comparator.
Figure 52:
Signal diagram of analog value comparator in Greater than/equal to mode
1: actual value at I7
2: setpoint plus hysteresis value
3: setpoint
4: setpoint minus hysteresis
The N/O contact switches if the actual value at I7 is equal to the setpoint
value. The N/O contact switches off when the actual value at I7 falls below
the setpoint minus hysteresis.
A5 GE
+
I1
I7
Æ
F1
+0
I2 0100
æ
F2 +0
OS +0
HY
0025
A5-------
Ä
Q1
→
The values
F1 +0
,
F2 +0
and
OS +0
were not defined. No
values are used with a gain factor, and no offset is used.
on
off
1
2
3
4
Summary of Contents for easy500, easy700
Page 4: ...II...
Page 28: ...1 1 5 operating principles 24 Operating instructions 05 10 MN05013003Z EN www eaton com...
Page 210: ...7 What Happens If 7 3 Event 206 Operating instructions 05 10 MN05013003Z EN www eaton com...
Page 234: ...9 Glossary of terms 230 Operating instructions 05 10 MN05013003Z EN www eaton com...