3 Commissioning
3.10 Commissioning an Net network
96
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
The configuration is successfully completed if the message on the left
appears. The NET menu is displayed again and the NET LEDs of all stations
flash. The NET is ready for operation.
▶
Press the ESC key to exit the menu.
During the NET configuration, all connected stations switch automatically to
STOP. The NET LED for the stations with NET ID 2-8 switches to OFF.
3.10.2.1 Possible error messages
The following messages may be output during the configuration:
Table 11: Possible messages during the configuration
Error message: ID conflict
An error message will appear if a station has a NET ID that does not
correspond to the physical location in the station list:
If you wish to correct the NET ID (
section “Change station list”, page
93), confirm the prompt with OK. Otherwise you can cancel the configuration
with ESC.
CONFIGURATION
IN
PROGRESS.
→
Any errors during the configuration are indicated by messages
or via the NET LEDs.
Further information can be found in following section and
section “Functionality of the NET faulty”, page 337.
Message
Meaning
ERR: ID CONFLICT
CONFIGURATION
CONFIGURATION ?
At least two NET stations have the same NET ID
ERR: TIME OUT
Network fault, for example if the cable is not correctly fitted or interrupted. Or you are
trying to assign NET ID 1 to a NET station, although a master with NET ID 1 is already
present on the NET.
Solution: Check the plug connection or the assigned NET IDs and restart the
configuration.