4 Wiring with 800
4.3 Loading a program on the 800-SWD device
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
103
4.3 Loading a program on the
800-SWD device
When commissioning easy800-SWD for the first time, the program must be
transferred from the PC and stored on easy800-SWD. The easySoft-Pro
software is required to complete the following steps.
▶
Connect the COM serial interface on easy800-SWD to the serial interface
of the PC (
Chapter 2, “Installation“, page 19 )
▶
Load the program and thus also the project configuration onto
easy800-SWD (see easySoft-Pro Online Help).
▶
Start easy800-SWD by selecting RUN mode.
Select RUN in the main menu on the device.
In easySoft-Pro click the buttons Communication ->
Program/Configurator->RUN.
•
POW-LED: green flashing
•
Config-LED: green continuous light
•
SWD-LED: green flashing
•
The SWD status LEDs on the two SWD stations are continuously lit
green.
If the project configuration matches the target configuration, the device
switches to operation and processes its circuit diagram. The actual
configuration was already stored as the target configuration when
SmartWire-DT was installed and is therefore identical.
4.4 Circuit diagram elements
A circuit diagram is a series of commands that the easy800 device processes
cyclically in RUN operating mode.
Coils and contacts are interconnected in the circuit diagram. In RUN mode, a
coil is switched on or off depending on the power flow and coil function set.
4.4.1 Function blocks
Function blocks are program blocks with special functions. Examples: Timing
relays, time switch, data block comparators. Function blocks are provided
with or without contacts and coils. How a safety or standard function block is
added to the safety or standard circuit diagram and parameterized is
described in
section 4.7, “Working with function blocks”, page 127 on.
In RUN mode the function blocks are processed according to the circuit
diagram and the results are updated accordingly.
Examples:
Timing relay = Function block with contacts and coils
Time switch = Function block with contacts