12 Appendix
12.3 Technical data
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
349
12.3.5 Inputs
12.3.5.1 Digital inputs 115/230 V AC
EASY819-AC-RC.
Digital inputs 115/230 V AC
Number
12
Status indicator
LCD display (if provided)
Potential isolation
from power supply
no
between digital inputs
no
from the outputs
yes
to PC interface (COM), memory card, network NET,
easyLink
yes
Rated operating voltage L (sinusoidal)
at signal ”0”
V AC
0 – 40
at signal ”1”
V AC
79 – 264
Rated frequency
Hz
50 – 60
Input current at signal "1"
I1 to I6, I9 to I12
m A
10 x 0.25 (at 115 V AC, 60 Hz)
10 x 0.5 (at 230 V AC, 50 Hz)
I7, I8
m A
2 x 4 (at 115 V AC, 60 Hz)
2 x 6 (at 230 V AC, 50 Hz)
Delay time
Delay time (0 – 1/1 – 0) I1 - I6, I9 - I12
Debounce ON, 50/60 Hz
ms
80
⁄
66
⅔
Debounce OFF, 50/60 Hz
ms
20
⁄
16
⅔
Delay time I7, I8 (1 – 0)
Debounce ON, 50/60 Hz
ms
120
⁄
100
Debounce OFF, 50/60 Hz
ms
40
⁄
33
⅓
Delay time I7, I8 (0 –> 1)
Debounce ON, 50/60 Hz
ms
80
⁄
66
⅔
Debounce OFF, 50/60 Hz
ms
20
⁄
16
⅔
Max. admissible cable length (per input)
I1 to I6, I9 to I12
Debounce ON
m
Normally 100
Debounce OFF
m
Normally 60
I7, I8
m
Normally 100