7 SmartWire-DT
7.4 Errors on the SWD line
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
295
LEDs on the device
The SWD-LED indicates whether the actual configuration of the SWD line
matches the target configuration.
The Config LED shows the result of the configuration comparison between
the saved target configuration and the project configuration below.
The devices and station parameters are taken into account.
Table 20: LEDs of easy800-SWD
LEDs on the station
Table 21: LEDs on the relevant station
Further information is provided in the manual “SmartWire-DT - The System”
(MN05006002Z-EN).
LED
Status
POW
Off
no supply voltage at POW
green continuous light
easy800-SWD in STOP mode
Green flashing
easy800-SWD in RUN mode
SWD
Off
no supply voltage at POW
no target configuration present
green continuous light
Actual configuration = Target configuration
green flashing
Actual configuration is determined
Orange flashing
Target configuration is determined
Red flashing
a required station missing
One station too many
Target configuration
≠
Actual configuration
red continuous light
No SWD line present
No 15 V DC device voltage present
Config
Off
no project configuration present, because e.g.
• Initial Commissioning or
• Program in easy806-SWD was deleted
green continuous light
Target configuration = Project Configuration
Green flashing
The station of the project configuration was replaced by a
compatible station in the target and actual configuration.
red continuous light
Target configuration
≠
Project Configuration
LED
Status
LED device
Off
no 15 V supply voltage
green flashing
Waiting for addressing
green fast flashing
Error on station and diagnostic alarm is 1
green continuous light
Station matches the target configuration.