3 Commissioning
3.3 LED display
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
71
3.3 LED display
The following LEDs are provided on the front of the easy800 depending on
device type:
1. POW/RUN
2. NET
3. Config (only easy800-SWD)
4. SWD (only easy800-SWD).
LED POW/RUN
The POW/RUN LED indicates the state of the POW power supply as well as
the RUN or STOP operating mode.
LED NET (
Net)
The NET LED provides information on the status of the Net
(
Section “Functionality of the NET faulty“, Page 337).
Config. LED
The Config LED indicates that the project configuration and target
configuration of the device match.
Table 7: Config.-LED (only easy800-SWD)
LED SWD (SmartWire-DT)
The SWD LED indicates whether SmartWire-DT is operating error-free.
Table 8: LED SWD (only easy800-SWD)
LED off
No supply voltage
LED green continuous light
STOP operating mode, supply voltage present
LED green flashing
RUN operating mode, supply voltage present.
LED off
NET not operational, fault in configuration.
LED green continuous light
Fault! Net is initialized but at least one station has not been detected.
LED green flashing
NET operating fault-free
LED off
no project configuration present, because e.g.
• Initial Commissioning or
• Program in easy806-SWD was deleted
LED green continuous light
Target configuration = Project Configuration
LED red continuous light
Target configuration
≠
Project Configuration
No SWD line present
LED off
no supply voltage at POW
no target configuration present
LED green continuous light
Actual configuration = Target configuration
LED green flashing
Actual configuration = Target configuration during addressing