EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Assignment 6
Assignment
1..n, Assignment
List
-.-
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
Inverting 6
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
Assignment 7
Assignment
1..n, Assignment
List
-.-
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
Inverting 7
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
DISARMED Ctrl
Enables and disables the disarming of the relay outputs.
This is the first step of a two step process, to inhibit the
operation or the relay outputs. Please refer to
"DISARMED" for the second step.
Inactive,
Active
Inactive
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4Z X2]
Disarm Mode
CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4Z X2]
t-Timeout DISARM
The relays will be armed again after expiring of this time.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4Z X2]