EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Force Mode
By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]
t-Timeout Force
The Output State will be set by force for the duration of
this time. That means, for the duration of this time, the
Relay Output does not show the state of the signals that
are assigned on it.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]
Input States of RO-4ZI X
Name
Description
Assignment via
RO1.1
Module Input State: Assignment
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
RO1.2
Module Input State: Assignment
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
RO1.3
Module Input State: Assignment
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
RO1.4
Module Input State: Assignment
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
RO1.5
Module Input State: Assignment
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
www.eaton.com
101