EDR-5000
IM02602007E
Operating Panel (HMI)
HMI
Special Parameters of the Panel
The »Device Parameter/HMI« menu is used to define the contrast of the display, the maximum admissible edit time,
and the menu language (after expiration, all unsaved parameter changes will be rejected).
Direct Commands of the Panel
Parameter
Description
Setting range
Default
Menu path
Contrast
Contrast
0 - 100%
50%
[Device Para
/HMI]
Global Protection Parameters of the Panel
Parameter
Description
Setting range
Default
Menu path
t-max Edit/Access
If no other key(s) is pressed at the panel, after expiration
of this time, all cached (changed) parameters are
cancelled. The device access will be locked by falling
back into Read-only level Lv0.
20 - 3600s
180s
[Device Para
/HMI]
Display Off
The display back light will be turned off when this timer
has expired.
20 - 3600s
180s
[Device Para
/HMI]
www.eaton.com
202