EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Remote Reset
Enables or disables the option to acknowledge from
external/remote via signals (assignments) and
Communication.
Inactive,
Active
Active
[Device Para
/Ex Acknowledge]
Ack LED
All acknowledgeable LEDs will be acknowledged if the
state of the assigned signal becomes true.
Only available if: Remote Reset = Active
1..n, Assignment
List
-.-
[Device Para
/Ex Acknowledge]
Ack RO
All acknowledgeable Relay Outputs will be acknowledged
if the state of the assigned signal becomes true.
Only available if: Remote Reset = Active
1..n, Assignment
List
-.-
[Device Para
/Ex Acknowledge]
Ack Comm
Communication will be acknowledged if the state of the
assigned signal becomes true.
Only available if: Remote Reset = Active
1..n, Assignment
List
-.-
[Device Para
/Ex Acknowledge]
Scaling
Display of the measured values as primary, secondary,
or per unit values
Per unit values,
Primary values,
Secondary values
Primary values
[Operation
/General Settings]
Maint Mode
Activation Mode of the Arc Flash Reduction. Switching
into another mode is only possible when no Activation
Signal is active (pending).
Inactive,
Activation Manually,
Activation via
Comm,
Activation via DI
Inactive
[Service
/Maint Mode]
Maint Mode
Activated by
Activation Signal for the Arc Flash Reduction
Maintenance Switch
Only available if: Maint Mode Activated by = Activation
via DI
1..n, Dig Inputs
DI-8P X1.DI 7
[Service
/Maint Mode]
Program Mode
Program Mode
Either Bkr Open or
Close,
Bkr Open
Either Bkr Open
or Close
[System Para
/General Settings]