EDR-5000
IM02602007E
Installation and Wiring
Three-Side-View
Depending on the connection method of the communication system used, the
needed space (depth) differs. If, for instance, a D-Sub-Plug is used, it has to be
added to the depth dimension.
Even when the auxiliary voltage is switched-off, unsafe voltages remain at
the device connections.
Outline Projection Mount - Door Cut-out
The housing must be carefully grounded. Connect a ground cable (AWG
12-10 [4 to 6 mm
2
] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is
marked with the ground symbol (at the rear side of the device).
The power supply card needs a separate ground connection (AWG 14
[2.5 mm
2
] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.
www.eaton.com
26