EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Scale Factor 12
The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP
/Point map
/Analog Input]
Dead Band 12
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP
/Point map
/Analog Input]
Analog value 13
Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList
-.-
[Device Para
/DNP
/Point map
/Analog Input]
Scale Factor 13
The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP
/Point map
/Analog Input]
Dead Band 13
If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00%
1%
[Device Para
/DNP
/Point map
/Analog Input]
Analog value 14
Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList
-.-
[Device Para
/DNP
/Point map
/Analog Input]
www.eaton.com
330