EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Pickup (sensitive)
If the pickup value is exceeded, the module/element will
be started.
0.002 - 2.000In
0.02In
[Protection Para
/<1..4>
/I-Prot
/51X[1]]
Curve Shape
Characteristic
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
ANSI MINV
[Protection Para
/<1..4>
/I-Prot
/51X[1]]
t-multiplier
Time multiplier/tripping characteristic factor. The setting
range depends on the selected tripping curve.
0.02 - 20.00
51X[1]: 1
51X[2]: 2
[Protection Para
/<1..4>
/I-Prot
/51X[1]]
Reset Mode
Reset Mode
Instantaneous,
t-delay,
Calculated
Calculated
[Protection Para
/<1..4>
/I-Prot
/51X[1]]
t-reset
Reset time for intermittent phase failures (INV
characteristics only)
Only available if:Reset Mode = t-delay
0.00 - 60.00s
0.00s
[Protection Para
/<1..4>
/I-Prot
/51X[1]]