EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
t-D1
Dead time between trip and reclosure attempt. Can be
initiated either by a phase or a ground fault.
Only available if: Shots = 1-6
0.01 - 9999.00s
1s
[Protection Para
/<1..4>
/AR
/Shot Manager
/Shot 1]
t-D2
Dead time between trip and reclosure attempt. Can be
initiated either by a phase or a ground fault.
Only available if: Shots = 2-6
0.01 - 9999.00s
1s
[Protection Para
/<1..4>
/AR
/Shot Manager
/Shot 2]
t-D3
Dead time between trip and reclosure attempt. Can be
initiated either by a phase or a ground fault.
Only available if: Shots = 3-6
0.01 - 9999.00s
1s
[Protection Para
/<1..4>
/AR
/Shot Manager
/Shot 3]
t-D4
Dead time between trip and reclosure attempt. Can be
initiated either by a phase or a ground fault.
Only available if: Shots = 4-6
0.1 - 9999.00s
1s
[Protection Para
/<1..4>
/AR
/Shot Manager
/Shot 4]
t-D5
Dead time between trip and reclosure attempt. Can be
initiated either by a phase or a ground fault.
Only available if: Shots = 5-6
0.01 - 9999.00s
1s
[Protection Para
/<1..4>
/AR
/Shot Manager
/Shot 5]
t-D6
Dead time between trip and reclosure attempt. Can be
initiated either by a phase or a ground fault.
Only available if: Shots = 6
0.01 - 9999.00s
1s
[Protection Para
/<1..4>
/AR
/Shot Manager
/Shot 6]
t-ManualCloseBlock This timer will be started if the Breaker was switched on
manually. While this timer is running, AR cannot be
started.
0.01 - 9999.00s
10.0s
[Protection Para
/<1..4>
/AR
/General Settings]