EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
V< Drop Out
Drop Out (is in percent of setting)
Only available if: Device Planning: V.Mode = V<
101 - 110%
103%
[Protection Para
/<1..4>
/Main-V-Prot
/27M[1]]
t
Tripping delay
0.00 - 3000.00s
0.00s
[Protection Para
/<1..4>
/Main-V-Prot
/27M[1]]
LOP Blo
Activates the use of the measuring circuit supervision. In
this case the module will be blocked if a measuring circuit
supervision module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse failure).
Inactive,
Active
Active
[Protection Para
/<1..4>
/Main-V-Prot
/27M[1]]
www.eaton.com
612