EDR-5000
IM02602007E
Setting Group Parameters of the Frequency Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
81O-Over
Pickup value for overfrequency.
Only available if: Device Planning: 81.Mode = 81O-Over
Or 81OR- Over & df/dt Or 81ODR- Over & DF/DT
40.00 - 69.95Hz
61.0Hz
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
81U-Under
Pickup value for underfrequency.
Only available if: Device Planning: 81.Mode = 81U-Under
Or 81UR- Under & df/dt Or 81UDR- Under & DF/DT
40.00 - 69.95Hz
59.0Hz
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
t
Tripping delay
Only available if: Device Planning: 81.Mode = 81U-Under
Or 81O-OverOr 81OR- Over & df/dt Or 81UR- Under &
df/dt
0.00 - 3600.00s
1.00s
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
www.eaton.com
689