EDR-5000
IM02602007E
Setting Group Parameters of the Reconnection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ReCon
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ReCon
/General Settings]
LOP Blo
Activates the use of the measuring circuit supervision. In
this case the module will be blocked if a measuring circuit
supervision module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse failure).
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ReCon
/General Settings]
V Ext Release PCC
Fc
Activate the release signal of the Point of Common
Coupling. The line-to-line voltage is greater than 95% of
VN.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ReCon
/General Settings]
Reclosure Release
Cond
This parameter ensures that the mains voltage is
recovered.
V Internal Release,
V Ext Release PCC
V Internal
Release
[Protection Para
/<1..4>
/ReCon
/Release Para]
PCC Fuse Fail VT
Fk
Blocking if the fuse of a voltage transformer has tripped
at the PCC.
Only available if: Reclosure Release Cond = V Ext
Release PCC
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ReCon
/Release Para]
VLL> Release
Minimum voltage (line-to-line) for reclosure (Restoration
Voltage)
Only available if: Reclosure Release Cond = V Internal
Release
0.70 - 1.00Vn
0.95Vn
[Protection Para
/<1..4>
/ReCon
/Release Para]
VLL< Release
Maximum voltage (line-to-line) for reclosure (Restoration
Voltage)
Only available if: Reclosure Release Cond = V Internal
Release
1.00 - 1.50Vn
1.10Vn
[Protection Para
/<1..4>
/ReCon
/Release Para]