EDR-5000
IM02602007E
Application Options of the Fault Simulator**:
Stop Options
Cold Simulation (Option 1)
Hot Simulation (Option 2)
Do not stop
Run complete:
Pre Failure, Failure, Post Failure.
How To?: Call up [S
ervice/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave
gen/Process
]
Ex Force Post = no assignment and
Press/Call up Start
Simulation.
Simulation without tripping the
breaker:
The TripCmd of all protection
functions will be blocked. The
protection function will possibly trip
but not generate a TripCmd.
How To?:
Call up [S
ervice/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine
wave gen/Process
]
Trip Cmd Mode = No TripCmd
Simulation is authorized to trip
the breaker:
How To?:
Call up [S
ervice/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine
wave gen/
Process]
Trip Cmd Mode = With TripCmd
Stop by external signal
Force Post: As soon as this signal becomes
true, the Fault Simulation will be forced to
switch into the Post Failure mode.
How To?: Call up [S
ervice/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave
gen/
Process]
Ex Force Post = Assigned Signal
Manual stop
As soon as this signal becomes true, the
Fault Simulation will be terminated and the
device changes back to normal operation.
How To?: Call up [S
ervice/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave
gen/
Process]
Press/Call up
Stop Simulation.
**Please note: Due to internal dependencies, the frequency of the simulation module is 0.16% greater than the rated one.