EDR-5000
IM02602007E
Technical Data
Use Copper conductors only, 75°C (167°F).
Conductor size AWG 14 [2.5 mm].
Climatic Environmental Conditions
Storage Temperature:
-30°C to +70°C (-22°F to 158°F)
Operating Temperature:
-20°C to +60°C (-4°F to 140°F)
Permissible Humidity at Ann. Average:
<
75% rel. (on 56d up to 95% rel.)
Permissible Installation Altitude:
<2,000 m (6,561.67 ft) above sea level
If 4,000 m (13,123.35 ft) altitude applies, a changed
classification of the operating and test voltages may be
necessary.
Degree of Protection
EN 60529
HMI Front Panel with Seal:
IP54
Rear Side Terminals:
IP20
Routine Test
Insulation Test Acc. to IEC60255-5:
All tests to be carried out against ground and other input and
output circuits.
Aux. Voltage Supply, Digital Inputs,
Current Measuring Inputs, Signal Relay
Outputs:
2.5 kV (eff.) / 50 Hz
Voltage Measuring Inputs:
3.0 kV (eff.) / 50 Hz
All Wire-Bound Communication
Interfaces:
1.5 kV DC
Housing
Housing B2: Height / Width
183 mm (7.205 in.)/ 212.7 mm (8.374 in.)
Housing Depth (Incl. Terminals):
208 mm (8.189 in.)
Material, Housing:
Aluminum
extruded section
Material, Front Panel:
Aluminum/Foil front
Mounting Position:
Horizontal (
±
45° around the X-axis must be permitted)
Weight:
Approx. 4.2 kg (9.259 lb)
www.eaton.com
901