EDR-5000
IM02602007E
www.eaton.com
945
t [s]
t-multiplier
Trip
Reset
x * Pickup
(Multiples of Pickup)
t =
19.61
*t-multiplier [s]
Pickup
-1
I
( )
2
+ 0.491
( )
t =
21.6
*t-multiplier [s]
Pickup
-1
I
( )
2
Notice!
Various Reset Modes are available . Resetting via characteristic, delayed, and
instantaneous .
ANSI VINV