IL05003005E.pdf
ELC-GP02
GRAPHIC PANEL SERIES
Instruction Sheet
WARNING
•
DANGER - DC input power must be disconnected before any maintenance. Do not connect or
disconnect wires and connectors while power is applied to the circuit. Maintenance must be
performed by qualified technicians.
•
DANGER - The ELC-GP02 requires 24VDC input power. The 24VDC input power should not be
connected to the RS-485 communication port. The unit may be destroyed or can’t be repaired if
the input power is improperly applied. Please always check the correctly input power wiring
before apply power.
•
DANGER - An electrical charge will remain on the DC-link capacitors for 1 minute after power
has been removed. Do not conduct any wiring or investigation on the ELC-GP02 until 1 minute
after power has been removed. Do NOT touch terminals when power on.
•
CAUTION - Always ground the ELC-GP02 by using the grounding terminal. Not only this acts as
a safety, but also filter out electrical noise. The ground method must comply with the laws of the
country where the unit is to be installed.
•
CAUTION - ELC-GP02 may be damaged if the fixed support (shipped with the pack) is adjusted
too tight.
•
Please carefully read this instruction before using the ELC-GP02.
•
The ELC-GP02 display panel is waterproof. But please prevent grease, corrosive liquids and
sharp objects from contacting the ELC-GP02.
•
Do not disconnect while circuit is live unless area is known to be non-hazardous.
•
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or Non-Hazardous
Locations only.
•
Explosion Hazard – Substitution of components may impair suitability for class I, Division 2.
•
Explosion Hazard – Do not disconnect equipment unless power has been switched off or the
area is known to be Non – Hazardous.
•
Power, input and output (I/O) wiring must all be in accordance with Class I, Division 2 wiring
methods, Article 501-4 (b) of the National Electrical Code, NEPA 70,or as specified in Section
18-152 of the Canadian Electrical Code for units installed within Canada, and in accordance
with that location’s authority.
1
INTRODUCTION
1.1 Model
Explanation
Thank you for choosing Eaton Logic Controler (ELC) GP series products. The features of ELC-GP02
are: resolution is 160*32, display 10*2 Chinese characters max. and Multilanguage support. Built-in
two communication ports (RS-232 and RS-485/RS-422, can be used simultaneously).
Communication and alarm indication LEDs. Extension slot for ELC-GPXFERMOD to copy settings
and programs rapidly and save download time. Built-in variety objects to meet your requirements.
1.2 Outline
1.3 Panel
Function
Explanation
PANEL COMPONENT
EXPLANATION
Alarm Indication LED
Status 1: When power is on, the LED will flash three times slowly.
Status 2: When there is an abnormal situation, the LED will flash quickly along with an
alarm sound.
RS-232 Indication LED
(Yellow)
It will be flashing when transmitting program and communicating by using RS-232.
RS-485 Indication LED
(Green)
It will be flashing when communicating by using RS-485.
LCM display Area
Liquid Crystal Module display area used to display current program state.
Esc Escape/Exit)
Used to cancel an incorrect input, or to Exit a programming step.
Arrow Keys
UP/Pg Up
: Used to increase the value or move up one page.
Pg Dn/DOWN
: Used to decrease the value or move down one page.
Left:
Left direction key. (move curser to left)
Right
: Right direction key. (move cursor to right)
Enter Key
Used to input a value or accept a programming command.
Function Keys
F0/0: It is used to be constant 0 and user can define the function of F0.
F1/1: It is used to be constant 1 and user can define the function of F1.
F2/2: It is used to be constant 2 and user can define the function of F2.
F3/3: It is used to be constant 3 and user can define the function of F3.
F4/4: It is used to be constant 4 and user can define the function of F4.
F5/5: It is used to be constant 5 and user can define the function of F5.
F6/6: It is used to be constant 6 and user can define the function of F6.
F7/7: It is used to be constant 7 and user can define the function of F7.
F8/8: It is used to be constant 8 and user can define the function of F8.
F9/9: It is used to be constant 9 and user can define the function of F9.
1.4 Back
Panel
5-PIN terminals:
Wire gauge: 12-24 AWG
Torque: 4.5 lb.-inch
1.5 Dimension
Front panel (unit: mm [inch])
Right side diagram (unit: mm [inch])
Vertical view (Unit: mm)
1.6 Installation
Mounting ELC-GP02 into the opening is done by carefully fitting the unit into the opening and
pressing firmly on all four corners. You could fix it by using the fixed support packaged with
ELC-GP02. You should infix the fixed support in the back cover and turn the screw in to fix.
Warning: If you turn the screw exceeds torque: 4-5(kg-cm), ELC-GP02 may be damaged.
(Note
:
the flat surface shoud be a Type 4 “Indoor Use Only” enclosure or equivalent.)
Please leave sufficient space (more than 50mm) around the unit for heat dissipation.
Thickness:
0.5~9.0mm
50mm
50mm
Mounting dimension (unit: mm [inch])
Thickness Range 0.5~9mm
135~136.5[5.31~5.37]
85
[3.35]
2
ELECTRICAL SPECIFICATION
2.1 Electrical
Specification
ITEM
ELC-GP02
Function Key / Digital Key
F0/0~F9/9, ESC, ENTER and ARROW keys
External Input Power
24VDC (-15%~20%) 3W MAX.
Memory Capacity
256K Byte
CPU Hitachi
MAX002
RAM of System
32K Byte
Communication Interface
COM1: RS-232 and COM2: RS-485
Waterproof Class of Front Panel
IP65/NEMA4/UL Type 4 (indoor use)
Environment Condition
0~50
℃
, relative humidity 20-90% RH
(
non-condensing
)
Storage Temperature of Hardware
-20~60
°
C
Vibration
5Hz
≦
f
<
9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hz
≦
f
≦
150Hz = Continuous: 0.5g / Occasional: 1.0g
Impact
15g peak, 11ms duration, half-sine, three shocks in each direction per
axis, on 3 mutually perpendicular axes (total of 18 shocks)
RF Radiation Test
CISPR11, Class A
Static Electricity Discharge Test
EN61000-4-2
RF Radiation Test
EN61000-4-3
High Frequency Transient Test
EN61000-4-4
Weight / Dimension
0.24kg / 147×97×35.5mm (Weight(W)×Height(H)×Deep(D))
Cooling Method
Natural Air-Cooling
Temperature Code
T6
Hazardous Location rating
Class I, Division 2, Group A, B, C, and D
2.2 Function
Specification
ITEM
ELC-GP02
Di
spla
y S
cree
n
Screen STN-LCD
Color Monochromatic
Back-light
The back-light automatic turn off time is 1~99 minutes
(0 = do not to turn off)
(back-light life is about 50 thousand hours at 25
℃
)
Resolution 160X32
dots