background image

- The diode is rated for maximum reverse voltage of 5 to 10 times the load voltage. 

- The forward current is more than the load current.

6

TRIAL RUN 

Ɓ

Power Indication 

The “POWER” LED at the front of the ELC will be lit (in green) if the power is on. 

Ŷ

Low Battery Voltage Indication 

There is also a “BAT.LOW” LED at the front of the ELC. When the LED is on, it indicates that the battery voltage is 

insufficient. Please change the battery (within 3 minutes) as soon as possible; otherwise the user programs and the 

data in latched area may be lost. 

Ŷ

Preparation 

1. Prior to applying power, please verify that the power lines and the input/output wiring are correct. And 

be advised not to supply AC110V or AC220V into the I/O terminals, or it might short-circuit the wiring 

and would cause direct damage to the ELC. 

2.  After using the peripheral devices to write the program into the ELC and that the ERROR LED of the 

ELC is not on, it means that the program in use is legitimate, and it is now waiting for the user to give 

the RUN command. 

3.  Use ELC-HHP to execute the forced On/Off test of the output contact. 

Ŷ

Operation & Test 

If the “ERROR” LED of the ELC is not blinking, use RUN/STOP switch or the peripheral devices (ELC-HHP or 

ELCSoft) to give the RUN command, and the RUN indicator will then be on. If the “RUN” LED is not on, it indicates 

that there is no program inside the ELC. 

ELC-HHP could be utilized to monitor the settings and the registered values of the timer (T), the counter (C) and the 

data register (D) during operation, and moreover, to force the output contacts to conduct the On/Off action. If the 

ERROR LED is on (but not blinking), it means that the setting of the user’s program has exceeded the preset 

overtime limit. At this time, please turn RUN/STOP switch to STOP and get program time-out address from special 

register D1008. (it is recommended to improve by WDT command) 

Ŷ

ELC Input/Output Reaction Time 

The total reaction time from the input signal to the output operation is calculated as follows: 

Reaction Time = input delay time + program scan time + output delay time 

Input delay time 

Factory setting is 10ms. Please refer to special registers D1020~1021. 

Program scan time 

Please refer to the usage of special register D1010. 

Output delay time 

Relay module: 10ms.    Transistor module: 20~30us. 

Ŷ

Basic Commands and Application Commands of the ELC: 

1.  The basic commands and the application commands of the ELC of this series are totally applicable to the 

ELC. Refer to the ELC Technique Application Manual for relevant basic commands and application 

commands. 

2.

The ELC-HHP handheld programming panel and the ELCSoft (Windows version) editing program of the 

ladder diagram are both good for use with the ELC. Also, the ELC could connect with the 

ELC-PC12NNDR/T,ELC-PC12NNAR through specific transmission wire to execute the program 

transmission, the ELC control and the program monitoring.

7

TROUBLESHOOTING 

Judge the errors by the indicators on the front panel.    When errors occurred on ELC, please check: 

Ɓ

“POWER” LED

There is a “POWER” LED at the front of the ELC. When the ELC is powered On, the green LED light will be on. 

Ɓ

ELC “RUN” LED

Identify the status of the ELC. When the ELC is in operation, this light will be on, and users could thus use 

ELC-HHP or the editing program of the ladder diagram to give commands to make the ELC “RUN” or “STOP”. 

Ɓ

“ERROR” LED

If incorrect programs are input to the ELC, the indicator will blink. Please check D1004(Error code) and 

D1137(Error step number). 

When the ERROR LED is on (not blinking), it indicates that the execution time of the program loop has 

exceeded the time-out setting (set by D1000). Please turn the ELC RUN/STOP switch to STOP, and find out the 

address of the time-out program by special data register D1008. ”WDT”. After completing modifying program, 

user only need to reload program and this LED will be off at this moment. Once the LED still lights, please turn 

off the power and check if there is interference or any conductive material in ELC. 

Ɓ

“BAT.LOW” LED

When the battery voltage is low, the “BAT.LOW” LED will be on, please change the battery within 3 minutes to 

retain the ELC’s internal user programs and data). 

Ɓ

“Input/Output” LED

The On/Off signals of the input point could be displayed through the “Input” LED. “Output” LED indicates if the 

output signals are On or Off.   

³5656´/('

³56´/('ZLOOOLJKWZKHQ56LVUHFHLYLQJGDWD³56´/('ZLOOOLJKW
ZKHQ56LVWUDQVIHUULQJGDWD