IL05003012E.pdf
5011630506-C206
2007-05-08
ELC-PC12NNDR/T
ELC-PC12NNAR
Logic Controller with Multi-Function,
Multiple Commands
Instruction Sheet
WARNING
•
This Instruction Sheet only provides descriptions for electrical specifications, general specifications,
installation & wiring, troubleshooting and peripherals. Other detail infromation about programming and
commands is compatible with ELC-PC/PA/PH series; please see ELC Application Manual. For more
information about the optional peripherals , please see individual product manual.
•
This is an OPEN TYPE Controller. The ELC should be kept in an enclosure away from airborne dust, humidity,
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tools or
keys to open the enclosure, so as to avoid the hazard to users and the damage to the ELC.
•
Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the
ELC. Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the ELC is
properly grounded
. Do NOT touch terminals when power on.
•
Battery replacement: use UL component type: TDRTL-2150/S lithium battery. Refer to following table for
battery life. (NOTE: RTC should be reset after changing battery).
Temperature((
°
C)
0 25 50 70
Life(Years)
9 8 6 5
Precision of calendar timer:
At 0
°
C/32
°
F, less than –117 seconds error per month.
At 25
°
C/77
°
F, less than 52 seconds error per month.
At 55
°
C/131
°
F, less than –132 seconds error per month.
•
Warning – Do not disconnect while circuit is live unless area is known to be non-hazardous.
•
Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods - Article
501-10(B)(1) of the National Electrical Code.
•
Suitable for use in Class 1, Division 2, Groups A, B, C, D or Non-Hazardous locations only.
•
Warning – Explosion hazard - Substitution of components may impair suitability for Class 1, Division 2.
•
Warning – Wxplosion hazard - Do not disconnect equipment unless power has been switched off or the area
is known to be Non-Hazardous.
1
INTRODUCTION
1.1 Model Name Explanation and Peripherals
Thank you for choosing Eaton Logic Controller (ELC) series products. The ELC-PC series has a 12-points (8 input
4 outputs) ELC main processing unit with multiple commands for use. It also has an 8K Steps program
memory to connect to every ELC-PC series expansion unit, including digital I/O (Maximum 128 Inpus / 128 Outputs
expansion points), analog module, etc. for various applications.
1.2 Product Profile and Outline
E
L
C
-P
C
12N
N
A
R
Y3
RS
-2
32
RS
-4
85
Y1
Y2
C2
Y0
C1
RUN
RUN
ERROR
POWER
Unit: mm
Warning: Battery replacement: Please change the battery within 3
minutes, or the internal data of the ELC (including the program area,
perpetual calendar and latched registers) could be lost or destroyed.
1 Status indicator: POWER, RUN,
ERROR, BAT.LOW
2 RUN/STOP switch
3 VR0: M1178 Start-up/D1178
Corresponding value
4 VR1: M1179 Start-up/D1179
corresponding value
5 DIN rail clip
6 I/O terminals
7 I/O point indicators
8 COM1 (RS-232) (Rx) indicator
9 COM2 (RS-485) (Tx) indicator
10 COM1 (RS-232) programming port
11 Nameplate
12 Expansion port
13 Mounting hold of the expansion unit
14 DIN rail (35mm)
15 Expansion unit clip
16 COM2 (RS-485) Communication port
17 DC Power input
18 2 pin removable terminal (standard
accessory)
19 Power input cable (standard
accessory)
20 Battery Cover
21 Battery socket connection
22 Battery mount
2
FUNCTION SPECIFICATIONS
Items
Specifications
Remarks
Control Method
Stored program, cyclic scan system
I/O Processing Method
Batch processing method (when END command
is executed)
I/O refresh command is
available
Execution Speed
Basic commands (several us)
Application Commands
(10~hundreds us)
Program Language
Co Ladder Logic + SFC
Including the Step commands
Program Capacity
7,920 STEPS
SRAM + Battery
Commands
32 Basic sequential commands 168
Application
commands
Rela
y (bit
mode)
X External Input Relay
X0~X177, octal number system, 128
points
Total
256
points
Correspond to external I/P
point
Y External Output Relay
Y0~Y177, octal number system, 128
points
Correspond to external O/P
point
M
Auxiliary
Relay
General
M0~M511, 512 points (*1)
Total
4,096
points
Contacts can switch to On/Off
in program
Latched
M512~M999, 488 points (*3)
M2000~M4095, 2,096 points (*3)
Special
M1000~M1999, 1,000 points (some are
latched)
T Timer
100ms
T0~T199, 200 points (*1)
Total
256
points
When the timer that set by
TMR command reaches the
preset value, the T contact with
the same number will be On.
T192~T199 for Subroutine
T250~T255, 6 points Accumulative (*4)
10ms
T200~T239, 40 points (*1)
T240~T245, 6 points Accumulative (*4)
1ms
T246~T249, 4 points Accumulative (*4)
C Counter
16-bit Count
Up
C0~C95, 96 points (*1)
Total
250
points
When the counter that set by
CNT (DCNT) command
reaches the preset value, the C
contact with the same number
will be On.
C96~C199, 104 points (*3)
32-bit Count
Up/Dn
C200~C215, 16 points (*1)
C216~C234, 19 points (*3)
32bit
High-speed
Count Up/Dn
C235~C245, 1 ph, 1 input, 9 points (*3)
C246~C250, 1 ph, 2 input, 3 points (*3)
C251~C254, 2 ph, 2 input, 3 points (*3)
S
Step
point
Initial Step
Point
S0~S9, 10 points (*1)
Total
1,024
points
Usage device of step ladder
diagram (SFC)
Latched Range:
Start: D1214 (K512)
End: D1215 (K895)
Zero Point
Reset
S10~S19, 10 points (use with IST
command) (*1)
General
S20~S511, 492 points (*1)
Latched
S512~S895, 384 points (*3)
Alarm
S896~S1023, 128 points (*3)
Regi
ster (W
ORD d
at
a)
T
Current Value of the
Timer
T0~T255, 256 points
When the timer reaches the
preset value, the contact of
timer will be On.
C
Current Value of the
Counter
C0~C199, 16-bit counter, 200 points
C200~C254, 32-bit counter, 50 points
When the counter reaches the
preset value, the contact of
counter will be On.
D
Data
Register
General
D0~D199, 200 points (*1)
Total
5,000
points
Can be memory area for
storing data. E and F can be
used as the special purpose of
index indication.
Latched
D200~D999, 800 points (*3)
D2000~D4999, 3,000 points (*3)
Special
D1000~D1999, 1,000 points
Index
E0~E3, F0~F3, 8 points (*1)
None
File Register
0~1,599 (1,600 points) (*4)
Expansion register for storing
data.
Pointer
N
For Master Control
Nested Loop
N0~N7, 8 points
Control point of master control
nested loop
P
For CJ, CALL
Commands
P0~P255, 256 points
The location point of CJ, CALL.
I
Inte
rrup
t Se
rvi
ce
External Interrupt
I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401
(X4), I501 (X5); 6 points (all are rising-edge
trigger)
The location pointer of interrupt
subroutine
Time Interrupt
I6
(1ms), I7
(1ms), (
1~99ms)
*1: The non-latched area is fixed, and can’t be changed.
*2: The non-latched area can be changed to a latched area with parameter setting.
*3: The latched area can be changed to a non-latched area with parameter setting.
*4: The latched area is fixed, and can’t be changed.
M
Auxiliary
Relay
General
Latched
Special auxiliary relay
Latched
M0~M511 M512~M999
M1000~M1999 M2000~M4095
Non-latched (fixed)
Latched (default)
Some are latched and
can’t be changed
Latched (default)
Start: D1200 (K512)
End: D1201 (K999)
Start: D1202 (K2,000)
End: D1203 (K4,095)
T
Timer
100 ms
10 ms
10ms
1 ms
100 ms
T0 ~T199
T200~T239
T240~T245 T246~T249 T250~T255
Non-latched (fixed)
Non-latched (fixed)
Accumulative Latched (fixed)
C
Counter
16-bit count up
32-bit count up/down
32-bit high-speed count up/down
C0~C95 C96~C199
C200~C215
C216~C234 C235~C245
C246~C255
Non-latched
(fixed)
Latched (default)
Non-latched
(fixed)
Latched (default)
Latched (default)
Start: D1208 (K96)
End: D1209 (K199)
Start: D1210
(K216)
End: D1211 (K234)
□□
□□
□□=
Hi-speed Counter I010, I020, I030, I040, I050, I060; 6 points
Communication
I150, 1 point
C
ons
ta
nt
K Decimal
K-32,768 ~ K32,767 (16-bit operation)
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation)
H Hexadecimal
H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation)
Programming Port
COM1: RS-232, COM2: RS-485 (Master/Slave), Can be used at the same time.
Analog Volume / Perpetual
Calendar (RTC)
ELC built-in 2 points VR / ELC built-in RTC
Special Expansion Module
Use the same modules of ELC series. (Max. 8 Expansion Unit points)
Start: D1212 (K235)
End: D1213 (K255)
S
Step Relay
For general Latched Special register
Latched
For general
S0~S9 S10~S19 S20~S511
S512~S895
S896~S1023
It is fixed to be non-latched
Factory setting is latched
It is fixed to be latched
Start: D1214 K512
(
)
End: D1215 K895
(
)
D
Register
General
Latched Special
registers Latched
D0~D199 D200~D999
D1000~D1999 D2000~D4999
Non-latched (fixed)
Factory setting is
latched.
Some are latched and
can’t be changed.
Factory setting is
latched.
Start: D1216 (K200)
End: D1217 (K999)
Start: D1218 (K2,000)
End: D1219 (K4,999)
File
Register
K0~K1,599
Latched (fixed)
When switching between power On/Off or ELC RUN/STOP modes:
Memory Type
POWER
Off
Ö
On
STOP
Ö
RUN
RUN
Ö
STOP
Clear all M1031
non-latched area
Clear all M1032
latched area
Factory
Setting
Non-latched Clear
Unchanged
M1033=Off, clear
Clear Unchanged
0
M1033=On,
unchanged
Latched Unchanged
Unchanged
Clear
0
Special M, Special
D, Index register Initial value
Unchanged
Unchanged
Initial
value
File register
Unchanged
0
3
ELECTRICAL SPECIFICATIONS
Model
Item
ELC-PC12NNDR/T
ELC-PC12NNAR
Power Supply Voltage
ELC: 24VDC (-15%~+20%) (With DC input reverse polarity protection),
Expansion Unit: supplied by the ELC
Fuse
2A / 250VAC
Power Consumption
3.5W MAX
Insulation Resistance
> 5 M at 500 VDC (Between all inputs / outputs and earth)
Ω
Noise Immunity
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of
terminals 24V and 0V (All ELC units should be grounded directly to the ground
pole).
Environment
Operation: 0 ~55 (Temperature), 50~95% (Humidity), Pollution degree 2;
℃
℃
℃
℃
Storage: -25 ~70 (Temperature), 5~95% (Humidity)
Agency Approvals
UL508
UL1604, Class1,Div2 Operating temperature code: T5
European community EMC Directive 89/336/EEC and Low Voltage Directive
73/23/EEC
Vibration / Shock Resistance
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27 (TEST
Ea)
Weight (approx.) (g)
158
DC Input Point Electrical Specification
Input Type
DC (SINK or SOURCE)
Input Current
24VDC 5mA
Active Level
Off On
→
→
X0,X1: above18.5VDC
On Off
X0~X7: below 8VDC
X2~X7: above16.5VDC