Troubleshooting
(For further information, visit the www.eaton.com site or contact after-sales support.)
◗
The battery backup outlets
9
are not supplied with power.
◗
The connected devices are not
supplied when AC power fails.
◗
AC power is available, but the
UPS
operates on battery power.
◗
The filtered outlets
8
are not
supplied.
◗
Green button
13
flashes
frequently and audio alarm
beeps.
◗
Red LED
12
is on and the
audio alarm beeps every 30
seconds.
◗
Red LED
11
is on and the
audio alarm beeps every 30
seconds.
◗
Green LED
10
is off and the
filtered outlets
8
are supplied.
◗
The telephone line is disturbed
or modem access is not
possible.
◗
Red LED
11
flashes.
Problem
Diagnostic
Solution
◗
Button
13
is not lighted on.
◗
The devices are not connected to
the battery backup outlets
9
.
◗
Circuit breaker
14
, located under
the
UPS
, has been tripped by an
overload on the
UPS
output.
◗
The wall outlet is not supplied.
◗
Circuit breaker
14
, located under
the
UPS
, has been tripped by an
overload on the
UPS
output.
◗
The
UPS
frequently operates on
battery power because the AC
power source is of poor quality.
◗
The
UPS
battery backup outlets
9
are overloaded.
◗
A fault has occurred on the
UPS
.
The battery backup outlets
9
are
no longer supplied.
◗
Surge protection is no longer
provided.
◗
Surge protection on the telephone
line is no longer provided.
◗
The battery has reached the end
of its service life.
◗
Press button
13
and check that it
turns green.
◗
Connect the devices to the battery
backup outlets
9
.
◗
Disconnect excess equipment
and reset the circuit breaker
14
by
pressing the corresponding button.
◗
Supply power to the wall outlet.
◗
Disconnect excess equipment
and reset the circuit breaker
14
by
pressing the corresponding button.
◗
Have the electrical installation
checked by a professional or use
another wall outlet.
◗
Disconnect excess equipment
connected to the battery backup
outlets
9
.
◗
Call after-sales support.
◗
Call after-sales support.
◗
Disconnect the telephone line from
the wall outlet.
◗
Call after-sales support.
◗
Have the battery replaced.
1
2
3
4
5
6
7
8
9
10
Advanced customizing of your UPS:
Sensitivity to variations of the AC power supply
◗
Only to be used
if frequent switching to the
UPS
battery due to large variations in the AC supply
voltage.
◗
Accessing the programming mode: with the device
switched off, press button
13
for 6 s and release it
once LEDs
11 12 13
have come on.
◗
Display of the 3 possible voltage ranges according to
the status of LEDs
11
and
12
:
Audio alarm
◗
Possibility of deactivating the audio alarm when the
UPS
is operating on the battery.
◗
Accessing the programming mode: with the device
switched off, press button
13
for 11 s and release it
when the audio alarm sounds.
◗
Display of the 2 possible audio alarm modes:
Normal mode
(factory
configuration):
AC supply
between 184V
and 264V
Low range
mode:
AC supply
between
161V
and 264V
Low and high
range mode:
AC supply
between
161V
and
284V
◗
Memorizing the mode: 10 s after the last press of the
button.
◗
Memorizing the mode: 5 s after the last press of the
button.
Normal mode (factory
configuration):
the
UPS
emits a beep
every 10 s when operating
on its battery.
Silent mode:
the
UPS
emits a single
beep when switching to
battery operation and
then remains silent.
Normal mode
activated:
programming
by continuous
beep.
Silent mode
activated:
programming
by a beep every
second.
Change from one mode to another by successively
pressing button
13
while the sound is audible.
11
13
12
11
13
12
11
13
12
Change from one mode to another by successively
pressing button
13
while the sound is audible.
Summary of Contents for Ellipse 375
Page 2: ...2 3400774700 AG...