ii
User Manual
MN032006EN
Effective December 2017
415U Condor-long-range
wireless I/O and gateway
EATON
www.eaton.com
Documentation note
Eaton acquired Cooper Industries in November, 2012. “Cooper
Bussmann” may appear in some screen images within this guide.
ATTENTION
INCORRECT TERMINATION OF SUPPLY WIRES MAY CAUSE INTERNAL
DAMAGE AND WILL VOID THE WARRANTY. TO ENSURE THAT YOUR
415U-2 WIRELESS I/O AND GATEWAY ENJOYS A LONG LIFE, CHECK THIS
USER MANUAL TO VERIFY THAT ALL CONNECTIONS ARE TERMINATED
CORRECTLY BEFORE TURNING ON POWER FOR THE FIRST TIME.
CAUTION
TO COMPLY WITH FCC RF EXPOSURE REQUIREMENTS IN SECTION 1.1310
OF THE FCC RULES, ANTENNAS USED WITH THIS DEVICE MUST BE
INSTALLED TO PROVIDE A SEPARATION DISTANCE OF AT LEAST 20 CM
FROM ALL PERSONS TO SATISFY RF EXPOSURE COMPLIANCE.
DO NOT OPERATE THE TRANSMITTER WHEN ANYONE IS WITHIN 20 CM OF
THE ANTENNA. ENSURE THAT THE ANTENNA IS CORRECTLY INSTALLED IN
ORDER TO SATISFY THIS SAFETY REQUIREMENT.
Avoid
•
Operating the transmitter unless all RF connectors are secure
and any open connectors are properly terminated
•
Operating the equipment near electrical blasting caps or in an
explosive atmosphere
Note
: All equipment must be properly grounded for safe
operations. All equipment should be serviced only by a
qualified technician.
FCC notice
Part 15.19—This device complies with part 15 of the FCC rules.
Operation is subject to the following two conditions: (1) this device
may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause
undesired operation.
Part 15.21—The grantee is not responsible for any changes or
modifications not expressly approved by the party responsible for
compliance. Such modifications could void the user’s authority to
operate the equipment.
Part 15.105(b)—This equipment has been tested and found to
comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance
with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the
following measures:
•
Reorient or relocate the receiving antenna
•
Increase the separation between the equipment and receiver
•
Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected
•
Consult the dealer or an experienced radio/TV technician for help
Part 90—This device has been type accepted for operation by the
FCC in accordance with Part 90 of the FCC rules (47CFR Part 90).
See the label on the unit for the specific FCC ID and any other
certification designations.
Note
: This device should only be connected to PCs that are
covered by either a FCC DoC or are FCC certified.
Manufacturer
Model number
Coax kit
Net
ELPRO
UDP400-C
CC3/450
1 dB gain
ELPRO
BU-3/400
CC10/450
2.5 dB gain
ELPRO
BU-6/400
CC10/450
5.5 dB gain
ELPRO
YU3/400
CC10/450
3.5 dB gain
ELPRO
YU6/400
C10/450
6.5 dB gain
ELPRO
YU9/400
CC20/450
5 dB gain
ELPRO
YU16/400
CC20/450
10 dB gain
Safety notices
Exposure to RF energy is an important safety consideration. The
FCC has adopted a safety standard for human exposure to radio
frequency electromagnetic energy emitted by FCC regulated
equipment as a result of its actions in Docket 93-62 and OET
Bulletin 65 Edition 97-01.
Hazardous location notices
The 415U-2-C4-EX, 415U-2-C3-EX, 415U-E-C4-EX and 415U-E-C3-EX
comply with the following standards:
•
IEC 60079-0:2012/A11:2013
•
IEC 60079-15:2010
The 415U-2-C4-EX, 415U-2-C3-EX, 415U-E-C4-EX and
415U-E-C3-EX comply with Directive 2014/34/EU—ATEX
Directive Ex nA IIC T4 Gc –30 °C ≤ Ta ≤ +60 °C.
Special conditions
1) This equipment is designed to be installed as a
component in an enclosure that meets IP54.
2) This equipment is to be mounted in a vertical orientation
to facilitate effective heat dissipation.
WARNING: EXPLOSION HAZARD
DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED
OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
The 415U-2-C4-EX, 415U-2-C3-EX, 415U-E-C4-EX and
415U-E-C3-EX are suitable for use in Class 1, Division 2,
Groups A, B, C and D; Tamb –30° C to +60° C or
non-hazardous locations only.
This equipment shall be installed in accordance with
the requirements specified in Article 820 of the National
Electrical Code (NEC), ANSI/NFPA 70-2011. Section 820.40
of the NEC provides guidelines for proper grounding, and
in particular specifies that the antenna ground (shield) shall
be connected to the grounding system of the building, as
close to the point of cable entry as practical.
This equipment shall be installed in a restricted access
location, such as a dedicated equipment room or
service closet.
The earth/ground terminal of this equipment shall be
connected to earth ground in the equipment installation.
The external power supply installed with this equipment
shall be a listed, Class 2 power supply, with a rated output
between 15 Vdc and 30 Vdc, and minimum 3500 mA.