background image

32

User Manual 

MN032006EN

Effective December 2017

415U Condor-long-range 

wireless I/O and gateway 

  

EATON

 www.eaton.com

Sensitivity blocks

All I/O registers have a configurable sensitivity value that determines 

how much the register needs to change before a change-of-state” 

(COS) message is sent. All registers except the following have a 

default sensitivity value of 1: 

• 

The 12 analog inputs have a sensitivity of 1000 counts, 

or approximately 3% (1000 counts from a total range of  

32768 = 3.05%).

• 

The 24 floating point values have a default sensitivity of 0.5 units. 

• 

Inputs 38001–38004 will be 0.5 mA, inputs 38005–38012 will be 

in volts, and inputs 38013–38016 will be in hertz. 

A sensitivity value is needed for analog inputs in order to prevent 

the module from sending every single-bit change of an analog value, 

and subsequently saturating the radio channel with unwanted COS 

messages. If a lower sensitivity is required, you can adjust the 

sensitivity block. However, take care not reduce the sensitivity to 

the point where radio messages are so frequent (due to a sensitivity 

change) that it saturates the radio network. There is a fine line 

between adjusting system parameters to receive up-to-date data 

and overloading the radio communications. A total of 50 sensitivity 

blocks can be configured for different registers or different values. 
To change sensitivity blocks for a module, click 

Sensitivity Blocks

 in 

the project tree (see 

Figure 51

). The screen lists existing sensitivity 

blocks for this module. To add a new sensitivity block, click 

Add

. To 

edit an existing sensitivity block, select it in list on the right, and click 

Edit

. This displays the IO Edit screen (see 

Figure 52

) where you can 

change settings. To delete a sensitivity block, select it in the list and 

click 

Delete

.

Figure 51. Sensitivity block

Figure 52. Editing sensitivity block

First Register

Select the starting register for the sensitivity 

block.

Count

Select the number of consecutive registers to 

which the sensitivity applies.

Sensitivity

Select the amount that the register needs to 

change before a COS trigger occurs.

Summary of Contents for ELPRO 415U

Page 1: ...User Manual MN032006EN Effective Dec 2017 New information 415U Condor long range wireless I O and gateway Version 2 11 ...

Page 2: ...g measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Part 90 This device has been type accepted for operation by the FCC in accordance with Part 90 of the FCC rules 47CF...

Page 3: ...d Gateway User Manual version 2 11 which applies to configuration software version 2 1 0 10 and firmware version 2 11 This user manual covers models 415U 2 C and 415U E C and Hazardous Location models 415U 2 C EX and 415U 2 E C EX Follow instructions Read this entire manual and all other publications pertaining to the work to be performed before installing operating or servicing this equipment Pra...

Page 4: ...ation 18 Wireless Interface 18 Radio setup 18 Network settings 19 Filter settings 19 Unit details 19 Networking 20 Mappings 21 WIB configuration options 21 Adding or editing mapping parameters 22 Startup or force configuration 24 I O configuration 25 Analog inputs 27 Configuring using the embedded web configuration utility 49 Configuring the locale 50 Quick start basic device configuration 51 Chan...

Page 5: ... multiple times before setting the communications status of that message to fail For critical messages this status can be reflected on an output on the module for alert purposes The module will continue to try to establish communications and retry each time an update or COS occurs The 415U comes from the factory with ELPRO WIB Modbus TCP RTU and DNP3 protocols as standard WIB protocol provides pow...

Page 6: ...message can be comprised of multiple I O values referred to as a block of I O The messages use error checking and return acknowledgment for greater reliability Up to four attempts are made when transmitting the message over each hop of the radio path and if no acknowledgment is received a Comms indication can be flagged The on board I O includes eight discrete I O two single ended analog inputs tw...

Page 7: ...15U E C Power level and modulation The charts below show the radio power relative to the maximum radio power for the 415U 2 C and 415U 2 E C models The maximum radio power depends on the radio modulation mode selected Refer to Table 1 below to relate power level modulation and the power levels on the charts shown on the following pages Legacy compatability FSK BandWidth Data rate Max Tx Power Max ...

Page 8: ... rated current 500mA Use the de rating chart in figure xx below to limit the radio power and duty cycle depending on the expected maximum temperature Figure 5 415U 2 C Radio only Use this chart when operating without active I O and without the need to charge an SLA battery Operating from the SUP and SUP inputs All On Board I O circuits unused Use the de rating chart above to limit the radio power ...

Page 9: ...om your power supply to support battery charging Table 3 Additional current to support battery charging Supply voltage Vsup Current required Isup 17 Vdc 600 mA 24 Vdc 450 mA 30 Vdc 350 mA Formula 0 Powering expansion I O modules The 415U 2 allows connection of 115S Series modules to the RS 485 port to provide expanded I O capacity You can use the and connections on the 415U 2 to provide up to 500 ...

Page 10: ...ting data rates up to 96kb s on a 25kHz channel The 415U 2 C also supports FSK modulation for operation with Legacy 415U 2 H and 415U 2 L models In Legacy mode data is transmitted using direct frequency shift keying with either one or two bits per symbol 2FSK 4FSK This supports data rates of 9600 baud 2FSK and 19 200 baud 4FSK on a wide 25 kHz channel and 4800 baud 2FSK and 9600 baud 4FSK on a nar...

Page 11: ...the main beam horizontal pointing in the forward direction If the Yagi antenna is transmitting to a vertically mounted omni directional antenna the Yagi elements should be vertical If the Yagi is transmitting to another Yagi the elements at each end of the wireless link need to be in the same plane horizontal or vertical Directional radomes should be installed with the central beam horizontal and ...

Page 12: ...rt supports Modbus protocol The RS 232 port is accessed using an RJ 45 connector wired as a DCE according to the EIA 562 Electrical Standard Table 2 RJ 45 connector RJ 45 Signal Required Signal name Connector 1 RI Ring Indicator 2 DCD Data Carrier Detect 3 DTR Y Data Terminal Ready 4 GND Y Signal Common 5 RXD Y Receive Data from module 6 TXD Y Transmit Data to module 7 CTS Clear to Send 8 RTS Requ...

Page 13: ...loading logged data files For details see To perform a full firmware upgrade using USB flash drive on page 82 Also see Data logging on page 64 DIP switches The DIP switches are used to select a number of functions within the module as shown in the following table DIP switches 1 to 2 Used for measuring current or voltage on analog input 3 Set DIP switches to on to measure current 0 20 mA and off fo...

Page 14: ...cted to a GND Figure 15 Digital pulsed input wiring Digital inputs 1 4 can be used as pulsed inputs The maximum pulse frequency is 50 kHz for input 1 and 2 and 1 kHz for input 3 and 4 Digital pulsed inputs are suitable for TTL signal level NPN transistor switch devices or voltage free contacts a relay or switch with debounce capacitor Frequencies greater than 1 kHz need to use a TTL logic drive or...

Page 15: ...puts The 415U 2 module provides two floating differential analog inputs and two grounded single ended analog inputs Analog inputs 1 and 2 will automatically measure current 0 20 mA or voltage 0 25 V depending on what is connected to the input Analog inputs 3 and 4 must be configured to measure current 0 20 mA or voltage 0 5 V via the DIP switches on the configuration panel see Side access configur...

Page 16: ...2 single ended current inputs Single ended current input mode is useful if the sensor loop is grounded to the 415U 2 module Devices can be powered from the 24 V analog loop supply ALS generated internally from the module The DIP switches located in the side access panel are used to determine if the inputs will be current or voltage DIP switches 1 and 2 are used for analog 3 and DIP switches 3 and ...

Page 17: ... outputs This is a configurable time value for each output If a message has not been received for this output within the configured time the output will assume a configured value We suggest that this reset time be a little more than twice the update time of the input It is possible to miss one update message because of short term interference However if two successive update messages are missed lo...

Page 18: ...es the most flexibility in configuring how your network connects but also comes with the greatest risk of configuring a network that performs poorly or not at all Manual mode networking uses the concept of Network Endpoints which are either Access Point or Client 802 11 networking Each client will connect to an access point with matching SSID Each access point can accept connections from several c...

Page 19: ...above you should configure Easy Filter at your Base Station to cover the 415U radio network and the Other Host devices but not the Base Network Figure 27 Easy filter Routed networks Sometimes it is necessary to configure the radio as an IP router to support desired addressing or address segmentation For this type of network you need to assign different Sub networks separate subnetwork addresses No...

Page 20: ...alled previously in addition to the new version Connecting to the device s USB port The USB port is located on the bottom side of the module Refer Figure 11 Bottom Panel Connections To connect you need an USB cable USB A to USB B for connecting from your computer to the module s USB B port If you have installed the Windows based Configuration Utility then USB drivers should have been installed at ...

Page 21: ...ngs on page 68 Select an option from the Communications panel such as Program Unit You will be presented with a connection dialog Figure 30 Select option Ethernet and enter the Device s IP Address Enter your User Name and Password and click OK Configuring your System using the PC Based Configuration Utility Once you have installed and started the configuration utility you can begin to configure yo...

Page 22: ... that slow down device connection AES 256 bit is the best option unless there is a specific reason to use the standards based encryption Note N Selecting Encryption None makes your network vulnerable to attack Without encryption there is no protection from attackers with access to the same type of hardware Encryption passphrase This is the secret key for your network encryption All devices in the ...

Page 23: ...er name Select the username to access this device The default configuration for the manager login is user Password Enter the password you configured for this module The factory default password is user Load unit Allows you to read the configuration data from the module radio and load it into MConfig replacing the configuration currently in MConfig for this module see Figure 34 Select the method yo...

Page 24: ...rward it on to another router that will Note IP routing is an advanced user function If you are not familiar with IP routing and your network consists of multiple sub networks connected by routers request assistance from an IT expert To display the IP routing rules table click Routing under Networking After configuring routing rules click the Program Unit button on the module s Unit Details screen...

Page 25: ... is 64 However if you are mapping digitals it can be as many as 1024 because the digitals values are packed into 16 bit words for transmission The mapping is sent on a change of state of any of the values being monitored and also on an update period Gather scatter mapping A gather scatter mapping is essentially the same as write mapping but instead of sequential register it allows different I O ty...

Page 26: ...ress This option allows any IP address to be entered in the configuration It is for advanced users only because the remote name and address location will not show up in the I O list Knowledge of the remote module s I O location and address is required for it to function correctly Generally this option is only used when a module that is not in the project is loaded or is being mapped to IO Table Al...

Page 27: ...ork Also the fail register can only be a digital output or internal bit registers 10501 501 and so on Enable Mapping Select the checkbox to enable this mapping Figure 37 Mapping advanced tab Invert When this checkbox is selected the signal is inverted before being sent to the remote end For analog signals the output signal is inverted around the 12 mA level For example after inverting a 12 mA sign...

Page 28: ...ured for the destination To configure a force register see the previous section Adding or editing mapping parameters on page 22 When the force register is activated any mapping configured with this force register will immediately send an update message to the destination so that its outputs can be set to the latest value It may be necessary to configure a startup or force message for each remote m...

Page 29: ...ersion of the 415U 2 The following registers are supported Address Input output description 0001 0002 Local DIO1 DIO2 as outputs 10001 10002 Local DIO1 DIO2 as inputs 10013 10015 Setpoint status from internal supplies 30005 Local supply voltage 0 40 V default scaling 30007 Local battery voltage 0 40 V default scaling 30008 115S expansion I O supply voltage 0 40 V default scaling 30013 30014 Local ...

Page 30: ...or the digital output or leave the default name The name can be up to 30 characters including spaces Fail safe Time sec Sets the time the output needs to count down before activating the fail safe state Receiving an update or a COS message will reset the fail safe timer to its starting value If the fail safe timer goes down to zero the output will be set to the fail safe state on or off It is reco...

Page 31: ... can also be used as voltage inputs by selecting DIP switches on the 415U 2 modules see DIP switches on page 9 To configure analog inputs click Analog Inputs under IO in the project tree Select a digital input from the list on the right and click Edit see Figure 43 This displays the IO Edit screen Figure 44 where you can change settings Figure 43 Analog inputs ...

Page 32: ... off the analog set point digital signals located at register 10009 10020 Note Set point values are entered in the scale of the input For example analog input 1 4 should be in mA analog inputs 9 12 should be volts and so on To control the set points use the Invert and Window control options described below All set points have these controlling options Invert Selecting this option inverts the set p...

Page 33: ...cters including spaces Fail safe Time sec Sets the time the output needs to count down before activating the fail safe state Receiving an update or a COS message will reset the fail safe timer to its starting value When the fail safe time elapses the output is set to the fail safe value mA It is recommend the fail safe time be configured for a little more than twice the update time of the input th...

Page 34: ...th address 16 Digital input 1 will be at register location 10321 Analog input 1 will be at register location 30321 For a detailed address map of the serial expansion I O modules see page 73 When adding expansion I O modules to the 415U 2 there are two inbuilt registers indicating the communication status of the expansion I O module Communication fail Located at register location 10019 offset value...

Page 35: ... before the fail timeout period expires Select Invalid or a desired value For digital registers the value can be either ON or OFF For analog registers select Enter Value to enter a value The value is set as a milli amp value or as a percentage The actual register value is displayed below the percentage setting Apply Saves the settings Note Don t use the failsafe for physical outputs For Physical o...

Page 36: ...tivity block However take care not reduce the sensitivity to the point where radio messages are so frequent due to a sensitivity change that it saturates the radio network There is a fine line between adjusting system parameters to receive up to date data and overloading the radio communications A total of 50 sensitivity blocks can be configured for different registers or different values To chang...

Page 37: ... IP address directly to the dashboard This simplifies access to the dashboard for users that are unfamiliar with the product If this button is left unchecked accessing the device will take users to the device s home page From the home page you can still access the dashboard by clicking a link to view the dashboard Page Title This is the title that will be displayed at the top of the dashboard view...

Page 38: ...splay for units Over Under Range Value Analog registers only If the displayed value moves beyond these thresholds the text Ovr or Und is displayed instead of the displayed value High Low Alarm If the displayed value moves beyond these values the dashboard item displays in red For Digital registers set these both to 0 to disable Set High alarm to 1 to alarm with ON state and set Low alarm to 1 to a...

Page 39: ... expansion modules are connected to the module Modbus RTU master To configure a module serial port as a Modbus RTU master click the serial port RS 485 or RS 232 in the project tree and then select Modbus RTU Master from the Operating Mode drop down menu see Figure 56 The Modbus RTU master should be configured if the 415U 2 is acting as a Modbus RTU master and polling Modbus slave devices via the s...

Page 40: ... MConfig Utilities menu Figure 57 Expansion I O Maximum No Expansion Modules to Poll Maximum number of slave addresses that the 415U 2 will scan or poll Default is 3 If adding more than 3 x 115S expansion I O module or the address used are greater than 3 this number will need to be increased to match the largest address Advanced Selecting the Advanced check box displays the Request Pause Response ...

Page 41: ... shared for both client and server For a full list of the available I O and address locations see To change Modbus configuration parameters click Modbus in the project tree The Modbus configuration screen Figure 58 is arranged in tabs The main tabs are Modbus TCP Server and RTU Slave Used for configuring Modbus TCP Server or RTU Slave parameters Modbus TCP Client and RTU Master Used for any Modbus...

Page 42: ...rver or to a Modbus RTU device connected to the serial port Care should be taken to ensure that all serially connected Modbus devices use different device IDs for example Modbus slave address and the device ID is different than the onboard device ID Up to 32 separate connections to the Modbus TCP server are supported Device ID The device ID for the modules own Modbus server slave This is the ID th...

Page 43: ...red For more information see Adding mapping parameters on page 40 RTU Master Allows you to configure Modbus RTU mappings to communicate with remote serial Modbus devices For more information see Adding mapping parameters on page 40 RS 232 Modbus Parameters Shows the configuration parameters for RS 232 ports See RS 232 RS 485 Modbus parameters on page 42 RS 485 Modbus Parameters Shows the configura...

Page 44: ...nes if the command will be Read or Write and what type of register will be used When entering a mapping you need to select Read or Write from the drop down list in the Command Type field and then select one of the four radio buttons representing the register types Selecting the register type will change the Destination slave register address range to a suitable range Destination Register Slave The...

Page 45: ...CP server port 502 and is configured with a response time of 1000 msec If it fails to communicate it will turn on local register 505 Modbus RTU master Modbus RTU functionality allows connections to Modbus RTU slave devices via the RS 232 or RS 485 ports Up to 100 mappings can be configured All Modbus mappings are directed to or from the onboard I O registers depending on the configuration describe...

Page 46: ...t to the wrong mode To change the mode click the RS 232 or RS 485 Modbus Parameter tab RS 232 RS 485 Modbus parameters The RS 232 and RS 485 Modbus Parameters tabs show the configuration parameters for the RS 232 and RS 485 ports These parameters are exactly the same as the serial parameters described in Serial configuration on page 35 These parameters are displayed under the Modbus tab for conven...

Page 47: ... disable DNP3 Connection Type Sets the connection type to match your DNP3 master connection UDP Uses UDP Protocol to communicate with the master TCP Listen Default This option uses TCP protocol to communicate with the master The device waits for a connection from the master TCP Dual Uses TCP protocol to communicate with the master If the device loses connection it attempts to connect to the master...

Page 48: ... only available when the Connection Type is set to UDP I O configuration You can change the way that I O data is reported by the 415U 2 DNP3 outstation By default all the on board I O report as polling class 0 only integrity poll To enable event reporting of the I O you need to configure the I O polling class You may also want to change the dead band parameter for analog and counter inputs and sca...

Page 49: ... memory map in the range 1 9999 Use the Add Edit and Delete buttons to edit the list To configure binary inputs or binary outputs click the option under DNP3 in the project tree Figure 69 Binary inputs and binary outputs DNP3 Index This is the DNP3 point index used to access the I O data from the DNP3 master device Register The I O point register in the 415U 2 device For a detailed description see...

Page 50: ... or 3 Once the counter generates a change event no additional events are generated until the counter value has changed by more than the dead band value Analog inputs The configuration for analog inputs defines how change events are reported dead band and how the value is scaled when it is reported The dead band value limits the number of event reports generated by the analog input when the input i...

Page 51: ... analog input scaling using the I O option in the project tree it will affect the scaling of DNP3 analog input points The DNP3 values are derived by applying this scaling to the register values after they are scaled by the device s analog scaling For more information on analog input scaling see Analog inputs on page 26 Dead Band The dead band value for the analog input expressed as a desired chang...

Page 52: ...om a 0 5 V analog input such as analog Inputs on 115S 13 configured for 0 5 V mode No Scaling Use this option when you want to write the raw register value from the DNP3 master without any scaling Custom Use this option to apply custom scaling Select the scaling option closest to the desired scaling then select Custom and enter values for the Register High Register Low Engineering High and Enginee...

Page 53: ... manager list Elpro 415U 2 USB Ethernet RNDIS Interface 5 Open your web browser recommended Internet Explorer version 10 or later and type http 192 168 111 1 into the browser bar The device s USB address is always the same The module responds with a username and password box 6 Type the username and password The default username is user and the default password is user This connects you to the home...

Page 54: ...Refer to the appendix for a list of supported Locales for each radio type If you intend to use the device in unlicensed operating mode select the appropriate Locale name from the table e g one of CZ NO SE ES in the example above WARNING USE OF UNLICENSED BANDS IS LIMITED TO THE LISTED PHYSICAL LOCALES ONLY ENSURE YOU SELECT A LOCALE THAT IS ALLOWED BY THE RADIO REGULATORY AUTHORITY IN YOUR TARGET ...

Page 55: ...ct one of Base Repeater or Remote These correspond to the roles in the image on the right of the screen For advanced applications with unusual connectivity requirements you can select Manual mode for additional networking options Normally a system will consist of a single Base zero or more Repeater s and multiple Remote s System Name This is a name common to every device in the system This allows ...

Page 56: ...Some countries Licensing rules require frequencies to be on 10 kHz or 20 kHz boundaries In these cases you should select 5 kHz to achieve the desired frequency Transmit Frequency This is the radio s transmit frequency in MHz The number will be automatically rounded to the closest available frequency based on the Frequency Step Size you selected Receive Frequency This is the radio s receive frequen...

Page 57: ... address of the devices connected to the radio network For the example above this would be 192 168 10 51 Last Radio Device IP This is the highest IP address of the devices connected to the radio network For the example above this would be 192 168 10 254 Note If you need to configure more complex filtering you can access this functionality from the IP filter configuration web page ...

Page 58: ...lows you to label the module This is also the DNS host name given to the module if it is used with a DHCP client Owner Module owner name Contact Contact details can include a phone number email address and so on Description Description of the module Location Physical location of the module Configuration Version The date and time when the module was last programmed System tools Click System Tools o...

Page 59: ... will be used Figure 77 Firmware upgrade Setting the date and time This feature is associated with data logging The module needs access to the current date and time to make effective use of data logging if this feature is enabled on the module see Data logging on page 64 To configure the date and time click System Tools on the menu and then click Set Date and Time This displays the page in Figure ...

Page 60: ...year and hour minute and second and click Pick again to set the time and close the pop up To set the time more precisely try selecting a time a little in the future and waiting until that time to click Pick Save Changes and Activate After configuring settings click Save changes and activate For manual time clicking this button sets the clock with the new time For NTP time after a short delay the m...

Page 61: ...tration mode The demonstration mode option on the Feature License Keys page Figure 79 temporarily allows full operation of all feature license options for 16 hours or until the module is restarted This allows you to try out the feature without purchasing the feature key When the demonstration period is up the module is restarted and demonstration mode is turned off To enable demonstration mode 1 C...

Page 62: ...les Operator Can view information on the device but cannot change configuration Manager Can view information and change the device configuration but cannot modify the list of users allowed to access the device Admin Has all of the permissions of a Manager plus the ability to modify the user list user passwords and access levels All users can change their own passwords The module comes from the fac...

Page 63: ... 1 Click User Management on the menu 2 In the Status column for the user click Retire 3 Click OK to confirm The user s status changes from Active to Retired 4 Click Save and Activate Changes This disables access to the module by the retired user To change a user password 1 Click User Management on the menu 2 In the Password column for the user click Change 3 Enter a new password for the user and c...

Page 64: ...of consecutive registers starting from the register location specified in the Register field Value Value to be written Read To read a register location enter an address location for example 10001 for digital inputs enter a count number of consecutive registers and then click Read Write To write to outputs enter the address location count and value and then click Write Watchdog error log The module...

Page 65: ...ing is enabled the statistics are logged to Analog Input Registers These are listed in detail in Input registers on page 73 Statistics registers provide the following information about the upstream connection Towards the base station If the module is configured as a base or configured in manual mode without any Client functionality then these registers will be zero RSSI The signal strength to the ...

Page 66: ...ock of 255 register locations For each downstream device the last byte of the device s IP address is used to determine which location to store the signal strength For example a downstream device with IP Address 192 168 0 199 will have its RSSI stored in I O register offset 199 If no device is connected with the IP address the register has the value Zero Monitoring communications Monitor IP comms o...

Page 67: ...e and size of the Ethernet frame Source IP Originating or source IP address Dest IP Destination IP address Len Total length of data Type Type of message for example Write Read Gather Scatter and so on Seq Sequence number of the message Ack Indicates whether the data frame is configured to acknowledge or not acknowledged This is configured in each mapping Dest I O address at the destination The des...

Page 68: ...te You need Administrator or Manager privileges to configure data and event logging Figure 86 Data and event logging configuration Data log configuration Scan Rate Enter the rate that you want data to be recorded fastest rate is every 5 seconds Records per File Enter the maximum number of records you want in a file up to 3 000 records per file When the maximum is reached the file is archived and a...

Page 69: ...based configuration utility The latest data is shown in a csv format on the screen Figure 88 Log information Retrieving logged data The module supports remote retrieval of files via HTTP as well as local retrieval of files via USB flash drive To retrieve logged data files via HTTP 1 Click Logs and Archives on the home page of the Web based configuration utility 2 Click the link Click to download d...

Page 70: ...ED turns green Figure 90 USB port 5 Remove the USB drive from the module USB port The log files are contained in a directory under the logs directory This subdirectory is named with the module device name or the module serial number if no device name was configured for the module The device name is configured on the Module Information configuration page The following example shows the contents of ...

Page 71: ...s Serial Settings 7 8 Data Bits Stop Start Parity Configurable Protocols and Configuration Protocols Supported TCP IP UDP HTTP FTP TFTP Telnet Modbus RTU Master Slave Modbus TCP Client Server WIB I O User Configuration All User Configurable Parameters via HTTP Configurable Parameters Unit details I O mappings and parameters For configuration details see in this manual Modbus TCP RTU Gateway Embedd...

Page 72: ...operation after you have completed configuration Otherwise the module will continue to boot into the default IP address Configuring PC networking settings Use this procedure to configure the PC networking settings needed in order to connect the PC to the module for configuration purposes 1 On the PC open the Control Panel and then click Network Settings The following description is for Windows XP ...

Page 73: ...nsmit 232 Green Transmitting RS 232 data 232 Red Receiving RS 232 data 232 Orange Transmitting and receiving RS 232 data 485 Green Transmitting RS 485 data 485 Red Receiving RS 485 data Additional 415U E LEDs LED Condition Meaning Green Strong signal suitable for 64QAM 4FSK Green Good signal suitable for 16QAM 4FSK Green Weak signal suitable for 4QAM 2FSK Yellow Very weak signal suitable for 4QAMF...

Page 74: ...t the fail safe state shown on the Digital Output Configuration page in the MConfig utility is off See Fail safe blocks on page 30 for details Analog inputs There are two LEDs for each differential analog input The first LED is used to indicate that the analog input is reading a current mA The second LED indicates that the input is reading voltage Each of the analog input LEDs will come ON when a ...

Page 75: ...nputs current mode AI1 and AI2 4 20 mA differential AI3 and AI4 4 20 mA sink 30005 Local supply voltage 0 40 V scaling 30006 Local 24 V loop voltage 0 40 V scaling 30007 Local battery voltage 0 40 V scaling 30008 115S supply voltage 0 40 V scaling 30009 30010 Local AI1 AI2 Voltage Mode 0 24V Scales to 0 24mA 30011 30012 Local AI3 AI4 Voltage Mode 0 5V Scales to 0 20mA 30013 30016 Local pulse input...

Page 76: ...e for 32 bit register values 36041 38000 Not Available 38001 38032 Local analog inputs as floating point values ModScan format sign exponent most significant 7 bits of significant at even higher addressed location lower 16 bits of significant at lower odd addressed location example Analog input 1 at 12 3 mA gives registers 38001 CCCD 38002 4144 38033 38040 Spare space for floating point values 380...

Page 77: ...S module 10020 Offset Modbus Comms Fail indication inverse for this 115S module 30001 Offset 30004 Offset 115S 11 pulsed input rate 1 4 30005 Offset 30012 Offset 115S 11 pulsed input count 30017 Offset Modbus Error counter for this 115S module 30018 Offset Modbus Last Error code for this 115S module see Expansion I O error registers on page 61 30019 Offset Modbus Lost Link counter for this 115S mo...

Page 78: ...dbus Error indication for 115S module 10020 Offset Detected indication for this 115S module 30017 Offset Modbus Error counter for this 115S module 30018 Offset Modbus Last Error code for this 115S module see Expansion I O error registers on page 61 30019 Offset Modbus Lost Link counter for this 115S module 30020 Offset Module type 0x0301 769 error status 40001 Offset 40008 Offset Analog output 1 8...

Page 79: ...Pulsed Input 4 Count 36007 36008 Pulsed Input 1 Rate 30013 Pulsed Input 2 Rate 30014 Pulsed Input 3 Rate 30015 Pulsed Input 4 Rate 30016 Pulsed Output 1 Count 46001 46002 Pulsed Output 2 Count 46003 46004 Pulsed Output 3 Count 46005 46006 Pulsed Output 4 Count 46007 46008 Analog Input 1 Floating Point mA 38001 38002 Analog Input 2 Floating Point mA 38003 38004 Analog Input 3 Floating Point mA 3800...

Page 80: ...al I O 12 10012 12 Digital I O 13 10013 13 Digital I O 14 10014 14 Digital I O 15 10015 15 Digital I O 16 10016 16 Analog I O 1 30001 40001 Analog I O 2 30002 40002 Analog I O 3 30003 40003 Analog I O 4 30004 40004 Analog I O 5 30005 40005 Analog I O 6 30006 40006 Analog I O 7 30007 40007 Analog I O 8 30008 40008 Pulsed I O Count 1 30017 30018 30009 30009 30009 Pulsed I O Count 2 30019 30020 30010...

Page 81: ...500 409 9875 27dBm 500mW 12 5 kHz Hong Kong 25 kHz ISM 1 433 0500 434 0400 10dBm 10mW 12 5 kHz 10 Region 1 ISM Band 1 25 kHz 10 ISM 2 434 0400 434 7900 10dBm 10mW 12 5 kHz Region 1 ISM Band 2 25 kHz ISM AUNZ 433 0500 434 7900 14dBm 25mW 12 5 kHz Australia and NZ ISM 25 kHz ISM ZA 433 0500 434 7900 20dBm 100mW 12 5 kHz South Africa ISM 25 kHz ISM ES 433 0750 433 3500 27dBm 500mW 12 5 kHz Spain ISM ...

Page 82: ...rogram The Modbus protocol is unaware of the significance of any particular value of any particular register 65384 FF04 Slave Device Failure An unrecoverable error occurred while the server or slave was attempting to perform the requested action 65285 FF05 Acknowledge Specialized use in conjunction with programming commands The server or slave has accepted the request and is processing it but sign...

Page 83: ...vels necessary to complete their job roles functions Category Description Restrict logical access to equipment Ensure default credentials are changed upon first login the 415U should not be commissioned for production with Default credentials it s a serious Cybersecurity flaw as the default credentials are published in the manuals No password sharing Make sure each user gets his her own password v...

Page 84: ...log files by plugging a Flash memory stick into the USB A port on the side of the module For more detail refer to the section Retrieving Logged Data on page 65 of this manual Secure maintenance Best practices Apply firmware updates and patches regularly Due to rapidly increasing Cyber Attacks on Industrial Control Systems Eaton implements a comprehensive patch and update process for its products U...

Page 85: ...ING SELECTING THE WRONG DRIVE COULD FORMAT YOUR PC S HARD DRIVE DISKPART select Disk 1 Disk 1 is now the selected disk 5 Enter the command list partition to check how the USB drive is partitioned This command indicates whether the drive is correctly configured for use as a firmware upgrade drive on the 415U 2 If the drive contains only one partition and the Offset value is non zero as shown in the...

Page 86: ...ware upgrade using USB flash drive 1 Connect to the module s Web based configuration utility and make a note of the current firmware version which appears on the home Web page This will enable you to compare versions to confirm that the upgrade procedure has been performed successfully Figure 100 Firmware version 2 Power off the 415U 2if it is currently powered on 4 Remove the cover from the small...

Page 87: ...ember 2017 415U Condor long range wireless I O and gateway EATON www eaton com Figure 102 Firmware upgrade LED indicators 8 When the upgrade is complete remove the USB flash drive from the module s USB port and replace the access panel cover ...

Page 88: ...ng the Program or a portion of it either verbatim or with modifications and or translated into another language Hereinafter translation is included without limitation in the term modification Each licensee is addressed as you Activities other than copying distribution and modification are not covered by this License they are outside its scope The act of running the Program is not restricted and th...

Page 89: ...on the recipients exercise of the rights granted herein You are not responsible for enforcing compliance by third parties to this License 7 If as a consequence of a court judgment or allegation of patent infringement or for any other reason not limited to patent issues conditions are imposed on you whether by court order agreement or otherwise that contradict the conditions of this License they do...

Page 90: ...E QUALITY AND PERFORMANCE OF THE PROGRAM IS WITH YOU SHOULD THE PROGRAM PROVE DEFECTIVE YOU ASSUME THE COST OF ALL NECESSARY SERVICING REPAIR OR CORRECTION 12 IN NO EVENT UNLESS REQUIRED BY APPLICABLE LAW OR AGREED TO IN WRITING WILL ANY COPYRIGHT HOLDER OR ANY OTHER PARTY WHO MAY MODIFY AND OR REDISTRIBUTE THE PROGRAM AS PERMITTED ABOVE BE LIABLE TO YOU FOR DAMAGES INCLUDING ANY GENERAL SPECIAL I...

Page 91: ...P uses an encryption key that automatically encrypts outgoing wireless data On the receiving side the same encryption key enables the computer to automatically decrypt the information so it can be read Encryption keys should be kept secret EIRP Equivalent isotropically radiated power EIRP or alternatively effective isotropically radiated power is the amount of power that a theoretical isotropic an...

Page 92: ... these smaller networks are used to simplify addressing between numerous computers Subnets connect together through a router Switch A type of hub that efficiently controls the way multiple devices use the same network so that each can operate at optimal performance A switch acts as a networks traffic cop rather than transmitting all the packets it receives to all ports as a hub does a switch trans...

Page 93: ...Cleveland OH 44122 United States Eaton com 2017 Eaton All Rights Reserved Printed in USA Publication No MN032006EN Z17944 December 2017 Eaton is a registered trademark All other trademarks are property of their respective owners ...

Reviews: