Statistics registers also record information about downstream
connections. These registers are used by all devices that have
downstream connections—Base station, Repeater, and Manual
Mode Access Points. For Manual Mode clients, and for Field Station
devices, these registers are unused and available as general
purpose storage.
RSSI List:
This is a block of 255 register locations. For each downstream device, the last byte of the device’s IP address is used to
determine which location to store the signal strength. For example, a downstream device with IP Address 192.168.0.199 will
have its RSSI stored in I/O register offset 199. If no device is connected with the IP address, the register has the value Zero.
Monitoring communications
Monitor IP comms on Ethernet port
Click
Monitor IP Comms
on the home page of the Web-based
configuration utility to view the IP communication data frames.
From here you can decode the data frame and read the transmitted
and received I/O values.
Figure 85. IP communication monitoring