background image

 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1875

EMERGENCY LIGHTING PRODUCTS

ELPSM22 system, ELPSM22 EXS/EXD system, ELPSM20 power supply,                      

EVLAM2 luminaire
Installation & maintenance information

!

IMPORTANT

Emergency lighting system should be installed, inspected, operated and 

maintained by qualified and competent personnel.

APPLICATION

The ELPSM22 emergency lighting system is designed to automatically provide 

illumination to designated areas during failure or interruption of power to the normal 

lighting system.  The ELPSM22 is factory assembled and wired, and consists of one 

(1) ELPSM20 power supply and two (2) EVLAM2 luminaires.

When properly installed, the following raintight ELPSM2 emergency lighting systems 

are UL and cUL Listed for use in:

• 

ELPSM20 power supply – Class I, Division 1, Groups B, C, D

• 

ELPSM22 – Class I, Division 1, Groups B, C, D

• 

Wet locations, Type 3R

• 

Ambient temperature = 0°C to 40°C

• 

Operating temperature code = T5

• 

Maximum mounting height = 9.3 ft.

Exit signs are not UL/cUL Listed:
• 

ELPSM22 (EXS/EXD)

• 

ELPSM2 EVI EMERGENCY LIGHTING EQUIPMENT (EXIT SIGN)

• 

ELPSM2 EVA GB EMERGENCY LIGHTING EQUIPMENT (GB [Group B] EXIT 

SIGN)

All ELPSM2 emergency lighting systems without exit signs are suitable for use in 

Class II, Division 1, Groups E, F, G and simultaneous presence hazardous (classified) 

areas as defined by the National Electrical Code

®

.

The ELPSM20 power supply consists of a battery supply and battery recharging 

system housed inside a hazardous area enclosure with all the circuitry to automatically 

turn on emergency DC lighting equipment when the normal power supply fails.  A 

pilot light indicates when normal power is being supplied to the unit.  A push-to-test 

pushbutton switch is provided for periodic testing of the unit.

Detail indication logic is given below:

Immediately after supply power is initiated, the indicating lamp will blink/pulse to 

indicate that the unit is charging.  Once installed with supply power, the ELPSM2 

requires 15 hours to charge the battery.  Once the unit has completed charging, the 

indicating light will stop blinking and go to steady.  Every six months, the unit will 

automatically perform a 90 minute battery discharge test.

At the completion of the test, if it is determined not to have met the 90 minute 

requirement, the indicating lamp will display circuit failure (3 blinks).  At any time, if the 

battery connection is not adequate, the indicating lamp will display a battery failure (2 

blinks).

The EVLAM2 luminaire is a factory sealed assembly housing a single LED lamp/

reflector light source. ELPSM2 EVI and ELPSM2 EVA GB exit signs are factory sealed 

with a single LED light source.  Lamps are included with all equipment.

Status indication

Status description

Status definition

No light

AC power removed from circuit

*

Steady light (no blinks)

Fully charged or test in process

* - *

Light blinks once

Battery charging

**-**

Light blinks twice

Battery failure

***-***

Light blinks three times

Circuit failure

****-****

Light blinks four times

Lamp failure

RATINGS

IF 1875 • 03/19                                                          Copyright

®

 2019, Eaton’s Crouse-Hinds Division 

                                                    Page 1

!

WARNING

To avoid personal injury, electric shock and equipment failure:

1. 

Do not use this equipment for other than intended use.

2. 

The use of accessory equipment not recommended by the manufacturer 

may cause an unsafe condition.

3. 

Electrical power must be turned OFF and the battery must be 

disconnected using the battery disconnect switch (if provided) before and 

during installation and maintenance.

4. 

Equipment should be mounted in locations where it will not readily be 

subjected to tampering by unauthorized personnel.

5. 

Do not mount near gas or electric heaters.

6. 

In Class I areas, install and seal all equipment in accordance with the 

National Electrical Code articles pertaining to hazardous (classified) 

locations, plus any other applicable codes.

7. 

Install only wiring systems with an equipment grounding conductor (which 

may be the conduit system) to supply the ELPSM2.

8. 

For safety in maintenance and servicing, a designated battery disconnect 

switch and a designated supply circuit disconnect switch must be installed.  

A main branch disconnect is suitable for disconnecting supply circuit.

9. 

Free installation area of hazardous atmospheres before wiring.

10.  Observe all battery handling precautions contained herein.
11.  Hammers or prying tools must not be allowed to damage the flat joint 

surfaces of the ELPSM20 power supply housing.  Do not handle covers 

roughly, or place them on surfaces that might damage or scratch the flat 

joint surfaces.

Table 1

Power supply

Input

• 120-277 VAC, 50/60 Hz

• 3.81 watts maximum

Output

• 12 VDC; 0.33 amperes maximum

• 4 watts maximum for 1 ½ hours

Lamp fixtures

Lamp model:

 

LEDTronics 

LEDG4BPF-1.5W-XIW-012V

(G4 2-pin base, 3000K)

• Input = 12 VDC, 1.5W

Lamp model:

 

Westinghouse 

33184 (G4 2-pin base, 3000K)

• Input = 12 VDC, 1.5W

STORAGE ENVIRONMENT

The ELPSM2 luminaire and accessories must be stored in an ambient temperature 

from 0°C to +40°C.  This includes units that have already been installed and may be 

powered down for extended periods of time (i.e. facility maintenance shutdowns).  

Store in a dry location.

IMPORTANT SAFEGUARDS – READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Summary of Contents for ELPSM22 EXD

Page 1: ...ealed assembly housing a single LED lamp reflector light source ELPSM2 EVI and ELPSM2 EVA GB exit signs are factory sealed with a single LED light source Lamps are included with all equipment Status i...

Page 2: ...1 sealing fitting must be installed within 18 inches of the conduit entry of the ELPSM2 enclosure Use Chico A or Chico SpeedSeal sealing compound to seal the conduit entry CAUTION To avoid damaging th...

Page 3: ...HAZARDOUS AREA YOU MUST INSTALL A CLASS I DIVISION 1 RATED SWITCH USE CROUSE HINDS SERIES EDS2129 OR EDSC2129 See Warning below This designated disconnect switch can be supplied as part of the ELPSM2...

Page 4: ...at A written record shall be kept of such tests and maintenance In the absence of periodic testing requirements by a local authority the following recommendations from the NFPA 101 2003 Life Safety Co...

Page 5: ...he push to test button 2 Loosen lens ring locking screw but do not remove See Figure 6 3 Remove lens by turning counterclockwise until all threads are disengaged 4 Pull lamp straight out of socket and...

Page 6: ...ewith MAINTENANCE RECORD NFPA 101 2003 REQUIREMENTS A FUNCTIONAL TEST SHALL BE CONDUCTED ON EVERY REQUIRED EMERGENCY LIGHTING SYSTEM AT 30 DAY INTERVALS FOR A MINIMUM OF 30 SECONDS AN ANNUAL TEST SHAL...

Page 7: ...en f brica que alberga una fuente nica de luz de reflector l mpara de LED Las se ales de salida de ELPSM2 EVI y ELPSM2 EVA GB son selladas en f brica con una fuente nica de luz LED Las l mparas se inc...

Page 8: ...lice el compuesto de sellado Chico A o Chico SpeedSeal para sellar la entrada del conducto PRECAUCI N Para evitar da os en las superficies planas de la junta no use martillos ni herramientas de palanc...

Page 9: ...gual a la de los cables de la fuente de alimentaci n de mayor voltaje de acuerdo con la secci n 300 3 C del NEC Importante PARA INSTALAR Y OPERAR ADECUADAMENTE EL ELPSM2 DEBE INSTALAR UN INTERRUPTOR D...

Page 10: ...ri dicas por una autoridad local se recomienda enf ticamente seguir las pautas del C digo de Seguridad Humana NFPA 101 2003 1 Mensual Opere un interruptor de prueba y mant ngalo presionado durante un...

Page 11: ...ar pero no lo retire Consultar la Figura 6 3 Retire los lentes al girar en contrarreloj hasta que todas las roscas est n desacopladas 4 Saque la l mpara directamente de la toma y deseche 5 Instale la...

Page 12: ...2003 SE LLEVAR A CABO UNA PRUEBA FUNCIONAL EN TODOS LOS SISTEMAS DE ILUMINACI N DE EMERGENCIA REQUERIDOS EN INTERVALOS DE 30 D AS DURANTE UN M NIMO DE 30 SEGUNDOS SE LLEVAR A CABO UNA PRUEBA ANUAL DE...

Page 13: ...et ELPSM2 EVA GB sont scell es en usine et pourvues d une seule source lumineuse DEL Les lampes sont comprises avec tout le mat riel Indicateur d tat Description de l tat D finition de l tat Le voyan...

Page 14: ...liser le mastic d tanch it Chico A ou Chico SpeedSeal pour sceller l entr e du conduit MISE EN GARDE Afin d viter d endommager les surfaces du joint plat ne pas utiliser de marteaux ou d outils levier...

Page 15: ...ssement ci dessous L interrupteur d isolement d sign peut tre fourni avec le syst me d clairage d urgence ELPSM22 options S794 et S854 Option S794 Interrupteur d isolement d sign cl int gr au syst me...

Page 16: ...ves des essais p riodiques les recommandations suivantes de la norme NFPA 101 2003 Life Safety Code sont fortement recommand es 1 Mensuellement Actionner le commutateur d essai et le maintenir enfonc...

Page 17: ...Desserrer la vis de blocage de la bague de la lentille sans l enlever Voir la figure 6 3 Retirer la lentille en tournant en sens antihoraire jusqu ce que tous les filets soient d sengag s 4 Tirer la l...

Page 18: ...UN ESSAI FONCTIONNEL D AU MOINS 30 SECONDES DOIT TRE EFFECTU SUR CHAQUE SYST ME D CLAIRAGE D URGENCE OBLIGATOIRE ET CE AU MOINS TOUS LES 30 JOURS UN ESSAI ANNUEL DOIT TRE EFFECTU POUR UNE DUR E D UNE...

Reviews: