internet) to the EMR-3MP0 has been made impossible. Please keep yourself informed
about up-to-date technology (firewalls, VPN etc.)!
1.4.3
Reset to Factory Defaults, Reset All Passwords
There is a dedicated Reset dialog that allows for selecting any of the following options:
• Reset to the factory defaults , or
• reset all passwords.
This Reset dialog is available at the HMI only (i. e. not via PowerPort-E).
Press the »Ack/Rst« key during a cold start until the Reset dialog appears.
NOTICE!
Note that the dialog might not appear at all because it has been intentionally disabled
(see below), or the option to reset all passwords has been disabled.
Reset to Factory Defaults
WARNING!
All parameter settings will be reset. All records will be deleted and statistic values and
counters will be reset.
Exception: The operation hours counter is preserved.
1. From the Reset dialog, select »Reset to factory default«.
⇨ There is a confirmation dialog, asking »Reset device to factory defaults and
reboot?«
2. Confirm with »Yes«.
⇨ The reset to factory defaults is executed, and the device restarts.
Reset All Passwords
It is possible to remove this option from the Reset dialog for security reasons (see below).
1. From the Reset dialog, select »Reset all passwords«.
⇨ There is a confirmation dialog, asking »Reset all passwords?«
2. Confirm with »Yes«.
⇨ The device starts using the standard password »1234«.
48
www.eaton.com
EMR-3MP0
1 EMR‑3MP0 Motor Protection Relay
1.4 Security