EMR-5000
IM02602012E
Global Protection Parameters of theAnalog Measuring Elements
Parameter
Description
Setting range
Default
Menu path
Updateinterv
Adjustable time between value updates
0.00 - 5s
0.04s
[Device Para
/Analog Inputs
/AnIn[1]]
Mode
The threshold depends to the mode/ mA or V
0...20 mA,
4...20 mA,
0...10V
0...20 mA
[Device Para
/Analog Inputs
/AnIn[1]]
Conversion Time
Conversion time needed by the ADC to sample input
values.
0.00 - 0.5s
0.01s
[Device Para
/Analog Inputs
/AnIn[1]]
Force Mode
For commissioning purposes or for maintanance. Analog
Inputs can be set by force. By means of this function the
normal Analog Inputs can be overwritten (forced).
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Inputs
/AnIn[1]]
t-Timeout Force
The Analog Input Value will be set by force for the
duration of this time. That means for the duration of this
time the Analog Input does not show the value of the
signals that are assigned on it.
Only available if: Force Mode = Active
0.00 - 300.00s
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Inputs
/AnIn[1]]
www.eaton.com