EMR-5000
IM02602012E
Setting Group Parameters of the Analog Alarm Elements
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Analog Inputs
/FldC[2]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Analog Inputs
/FldC[2]]
Pickup
Threshold
0.1 - 100.0%
20%
[Protection Para
/<1..4>
/Analog Inputs
/FldC[2]]
t
Tripping delay
0.00 - 10.00s
1s
[Protection Para
/<1..4>
/Analog Inputs
/FldC[2]]
Device Planning Parameters of the Analog Alarm Elements
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
FldC[2]: Do not
use
Pres[2]: Do not
use
Tmp[2]: Do not
use
Vibr[2]: Use
Spd[2]: Use
VBat[2]: Do not
use
AnaP[2]: Use
[Device Planning]
www.eaton.com
139