EMR-5000
IM02602012E
Configuration of the Average Value Calculation
Configuration of the Current Based Average Value Calculation*
*=Availability depends on the ordered device code.
Current based Average Values and Peak Values
Time period for the
calculation of the
average and peak values
Start options
Reset of the average and
peak values
Configuration Options
Where to configure?
In [Device Para\
Statistics\
Demand\
Current Demand]
sliding:
(sliding: average calculation
based on sliding period)
fixed:
(fixed: Average calculation is
resetted by the end of the period,
that means with the next starting
period)
duration:
(fixed or sliding period)
Start Fct:
(The average values are
calculated based on the time
period between two rising edges
ot this signal)
Res Fc
(e.g. via Digital Input in order to
reset the average values in
advance (before the next rising
edge of the start signal). This
applies to option „Start FC“ only.
Trip (command) option to limit
the average current demand:
Yes
Please refert to chapter „System Alarms“
View average values and peak
values
Where? Within menu [Operation\Statistics\Demand]
www.eaton.com
209