EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Threshold
Threshold (to be entered as primary value)
1 - 40000000kVA
20000kVA
[SysA
/Demand
/Power Demand
/VA Demand]
t-Delay
Tripping Delay
0 - 60min
0min
[SysA
/Demand
/Power Demand
/VA Demand]
Alarm
Alarm
Inactive,
Active
Inactive
[SysA
/Demand
/Current Demand]
Threshold
Threshold (to be entered as primary value)
10 - 500000A
500A
[SysA
/Demand
/Current Demand]
t-Delay
Tripping Delay
0 - 60min
0min
[SysA
/Demand
/Current Demand]
Alarm
Alarm
Inactive,
Active
Inactive
[SysA
/THD
/I THD]
Threshold
Threshold (to be entered as primary value)
1 - 500000A
500A
[SysA
/THD
/I THD]
t-Delay
Tripping Delay
0 - 3600s
0s
[SysA
/THD
/I THD]
Alarm
Alarm
Inactive,
Active
Inactive
[SysA
/THD
/V THD]
Threshold
Threshold (to be entered as primary value)
1 - 500000V
10000V
[SysA
/THD
/V THD]