EMR-5000
IM02602012E
Manual Resets
In the
»Operation/Reset« menu, the User can:
•
Reset counters;
•
Delete records (e.g.: waveform records); and
•
Reset special things (like statistics, thermal replica, etc.).
The description of the reset commands can be found within the corresponding
modules.
Manual Resets Via PowerPort-E
•
If PowerPort-E is not running, please start the application.
•
If device data have not been downloaded recently, click »Receive Data From The Device« in the »Device« menu.
•
Double click the »Operation« icon in the navigation tree.
•
Double click the »Reset icon« within the operation menu.
•
Double click the entry within the pop-up that is to be reset or deleted.
The description of the reset commands can be found within the corresponding
modules.
Reset to Factory Defaults
This Function will reset the device to the factory defaults.
All records will be deleted and and the measured values and counters will be
reset. The operation hours counter will be kept.
This Function is available at the HMI only.
•
Press the »Ack/Rst
-key«
during a cold start, in order to access the »
Reset«
menu.
•
Select »
Reset to factory default«
.
•
Confirm
»
Reset device to factory defaults and reboot«
with
»
Yes«
in order to execute the reset to factory
defaults.
«
www.eaton.com
249