EMR-5000
IM02602012E
How to Read Out the Fault Recorder Via
PowerPort-E
If
PowerPort-E
is not running, please start the application.
If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.
Double click the »Operation« icon in the navigation tree.
Double click the »Fault Rec« icon within the
»
Operation/Recorders« tree.
In the window, the fault recordings are shown in tabular form.
In order to receive more detailed information on a fault double click the selected item in the list.
Via the print menu, the User can export the data into a file. Please proceed as
follows:
•Call up the data as described above.
•Press the »Print« button.
•Press the »Export to File« button.
•Enter a file name.
•Choose a location where to save the file.
•Confirm the »Save« button.
How to Test the Fault Recorder
After generating an General Alarm Signal a fault record should be written.
www.eaton.com
269