EMR-5000
IM02602012E
DO NOT over-tighten the mounting nuts of the relay
(0.164 X32 ). Check the torque by means of a torque wrench (1.7 Nm [15
In-
lb
]). Over-tightening the mounting nuts could cause personal injury or damage
the relay.
Outline Standard Mount - Door Cut-out
The housing must be carefully grounded. Connect a ground cable (AWG
12-10 [4 to 6 mm
2
] / 15 In-lb [1.7 Nm]) to the housing, using the screw that
is marked with the ground symbol (at the rear side of the device).
The power supply card needs a separate ground connection (AWG 14
[2.5 mm
2
] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.
www.eaton.com
28