Trip Manager – Assignment of commands
The trip commands of the protection elements have to be assigned to those switchgear, that are make/break capable
(Breaker). For every make/break capable switchgear a Trip Manager is provided.
In the Trip Manger all tripping commands are combined by an “OR” logic. The actual tripping command to the
switchgear is exclusively given by the Trip Manager
. This means, that only tripping commands which are assigned in
the Trip Manager lead to an operation of the switchgear.
In addition to that, the User can set the minimum hold time of
the tripping command within this module and define whether the tripping command is latched or not.
Tripable Elements:
Name
Description
-.-
No assignment
MStart.TripCmd
Signal: Trip Command
50P[1].TripCmd
Signal: Trip Command
50P[2].TripCmd
Signal: Trip Command
50P[3].TripCmd
Signal: Trip Command
51P[1].TripCmd
Signal: Trip Command
51P[2].TripCmd
Signal: Trip Command
51P[3].TripCmd
Signal: Trip Command
50X[1].TripCmd
Signal: Trip Command
50X[2].TripCmd
Signal: Trip Command
51X[1].TripCmd
Signal: Trip Command
51X[2].TripCmd
Signal: Trip Command
50R[1].TripCmd
Signal: Trip Command
50R[2].TripCmd
Signal: Trip Command
51R[1].TripCmd
Signal: Trip Command
51R[2].TripCmd
Signal: Trip Command
87M[1].TripCmd
Signal: Trip Command
87M[2].TripCmd
Signal: Trip Command
50G[1].TripCmd
Signal: Trip Command
50G[2].TripCmd
Signal: Trip Command
51G[1].TripCmd
Signal: Trip Command
51G[2].TripCmd
Signal: Trip Command
49.TripCmd
Signal: Trip Command
50J[1].TripCmd
Signal: Trip Command
50J[2].TripCmd
Signal: Trip Command
37[1].TripCmd
Signal: Trip Command
37[2].TripCmd
Signal: Trip Command
www.eaton.com
424